Line
ID
Parameter
Name
Range
Default
Setting
Description
S254
Event Delay Time
(sec)
‒ ‒
Circuit 2 low pressure.Event Enabled Disabled Enabled Enabled
Event: CIRCUIT 2
LOW PRESS
MESSAGE WARNING ALARM ALARM
S255
Event Delay Time
(sec)
‒ ‒
Circuit 1 pump down failure.Event Enabled Disabled Enabled Enabled
Event: CIRCUIT 1
PUMPD. FAIL
MESSAGE WARNING ALARM ALARM
S256
Event Delay Time
(sec)
‒ ‒
Circuit 2 Pump down failure.Event Enabled Disabled Enabled Enabled
Event: CIRCUIT 2
PUMPD. FAIL
MESSAGE WARNING ALARM ALARM
S257
Event Delay Time
(sec)
‒ ‒
Digital scroll 1 high temperature.
Event Enabled Disabled Enabled Enabled
Event: DIG
SCROLL1 HIGH
TEMP
MESSAGE WARNING ALARM ALARM
S258
Event Delay Time
(sec)
‒ ‒
Digital scroll 2 high temperature.
Event Enabled Disabled Enabled Enabled
Event: DIG
SCROLL2 HIGH
TEMP
MESSAGE WARNING ALARM ALARM
S259
Event Reset Type
0 = AR
1 = MR
0 (AR)
Electric heat high temperature. AR = Auto Reset, MR = Manual
Reset.
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Event Enabled Disabled Enabled Enabled
Event: EL HEAT
HIGH TEMP
MESSAGE WARNING ALARM ALARM
S262
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Event Enabled Disabled Enabled Enabled
Working hours exceeded.
Event: UNIT HRS
EXCEEDED
MESSAGE WARNING ALARM WARNING
S263
Event Delay Time
(sec)
10 - 9999 sec 10 sec Smoke detected.
Table B.2 Service Menu Alarm Settings by Line ID (continued)
214
Vertiv™ Liebert® iCOM™Installer/User Guide