Line
ID
Parameter
Name
Range
Default
Setting
Description
Event: LOW TEMP
SENSOR A
MESSAGE WARNING ALARM WARNING
S245
Event Delay Time
(sec)
10 - 9999 sec 30 sec
High humidity sensor A.Event Enabled Disabled Enabled Disabled
Event: HIGH HUM
SENSOR A
MESSAGE WARNING ALARM WARNING
S246
Event Delay Time
(sec)
10 - 9999 sec 30 sec
Low humidity sensor A.Event Enabled Disabled Enabled Disabled
Event: LOW HUM
SENSOR A
MESSAGE WARNING ALARM WARNING
S249
Event Delay Time
(sec)
‒ ‒
Compressor 1 overload.Event Enabled Disabled Enabled Enabled
Event: COMP 1
OVERLOAD
MESSAGE WARNING ALARM ALARM
S250
Event Delay Time
(sec)
‒ ‒
Compressor 2 overload.Event Enabled Disabled Enabled Enabled
Event: COMP 2
OVERLOAD
MESSAGE WARNING ALARM ALARM
S251
Event Delay Time
(sec)
‒ ‒
Circuit 1 high pressure.Event Enabled Disabled Enabled Enabled
Event: CIRCUIT 1
HIGH PRESS
MESSAGE WARNING ALARM ALARM
S252
Event Delay Time
(sec)
‒ ‒
Circuit 2 high pressure.Event Enabled Disabled Enabled Enabled
Event: CIRCUIT 2
HIGH PRESS
MESSAGE WARNING ALARM ALARM
S253
Event Delay Time
(sec)
‒ ‒
Circuit 1 low pressure.Event Enabled Disabled Enabled Enabled
Event: CIRCUIT 1
LOW PRESS
MESSAGE WARNING ALARM ALARM
Table B.2 Service Menu Alarm Settings by Line ID (continued)
213
Vertiv™ Liebert® iCOM™Installer/User Guide