Line
ID
Parameter
Name
Range
Default
Setting
Description
Airflow Delay
Event Delay Time
(sec)
10 - 9999 sec 30 sec
Event Enabled Disabled Enabled Enabled
Event: LOSS OF
AIRFLOW
MESSAGE WARNING ALARM ALARM
S238
Event Delay Time
(sec)
10 - 9999 sec 10 sec
Clogged filters.Event Enabled Disabled Enabled Enabled
Event: CLOGGED
FILTERS
MESSAGE WARNING ALARM WARNING
S239
Event Delay Time
(sec)
10 - 9999 sec 30 sec
High room temperature.Event Enabled Disabled Enabled Enabled
Event: HIGH ROOM
TEMP
MESSAGE WARNING ALARM WARNING
S240
Event Delay Time
(sec)
10 - 9999 sec 30 sec
Low room temperature.
Event Enabled Disabled Enabled Enabled
Event: LOW ROOM
TEMP
MESSAGE WARNING ALARM WARNING
S241
Event Delay Time
(sec)
10 - 9999 sec 30 sec
High room humidity.Event Enabled Disabled Enabled Enabled
Event: HIGH ROOM
HUM
MESSAGE WARNING ALARM WARNING
S242
Event Delay Time
(sec)
10 - 9999 sec 30 sec
Low room humidity.
Event Enabled Disabled Enabled Enabled
Event: LOW ROOM
HUM
MESSAGE WARNING ALARM WARNING
S243
Event Delay Time
(sec)
10 - 9999 sec 30 sec
High temperature Sensor A.Event Enabled Disabled Enabled Disabled
Event: HIGH TEMP
SENSOR A
MESSAGE WARNING ALARM WARNING
S244
Event Delay Time
(sec)
10 - 9999 sec 30 sec
Low temperature Sensor A.
Event Enabled Disabled Enabled Disabled
Table B.2 Service Menu Alarm Settings by Line ID (continued)