Event Internal delay
Default delay/Range
for adjustment
Type
UNIT X DISCONNECTED Internal Calc. - WRN
LOSS OF POWER 0 sec no ALM
CUSTOMER INPUT 1 2 sec 2 sec/0 9999 * ALM
CUSTOMER INPUT 2 2 sec 2 sec/0 9999 * ALM
CUSTOMER INPUT 3 2 sec 2 sec/0 9999 * ALM
CUSTOMER INPUT 4 2 sec 2 sec/0 9999 * ALM
CALL SERVICE 2 sec 2 sec/0 9999 * MSG
HIGH TEMPERATURE 2 sec 2 sec/0 9999 * MSG
LOSS OF AIR BLOWER 1 2 sec 2 sec/0 9999 * ALM
REHEAT LOCKOUT 2 sec 2 sec/0 9999 * WRN
HUMIDIFIER LOCKOUT 2 sec 2 sec/0 9999 * WRN
FC LOCKOUT 2 sec 2 sec/0 9999 * WRN
COMPRESSOR(S) LOCKOUT 2 sec 2 sec/0 9999 * WRN
COMP 1 SHORT CYCLE 0 sec 0 9999 MSG
COMP 2 SHORT CYCLE 0 sec 0 9999 MSG
No Power 0 sec 0 sec/0 9999WRN
Condensate 1 Failure 0 sec 5 sec/0 9999 WRN
Condensate 2 Failure 0 sec 5 sec/0 9999 WRN
EC Fan Fault 0 sec 10 sec/0 9999 ALM
HIGH SUP TEMP 0 sec 30 sec/0 9999 WRN
LOW SUP TEMP 0 sec 30 sec/0 9999 ALM
REDUCED ECO AIRFLOW 0 sec 3 sec/0 9999 WRN
ECO HI TEMP OVERRIDE 0 sec 10 sec/0 9999 WRN
TEMP CTRL SENSOR FAIL 0 sec 3 sec/0 99999 ALM
HIGH DEW POINT 0 sec 30 sec/0 9999 WRN
LOW DEW POINT 0 sec 30 sec/0 9999 WRN
HI DEW POINT SENSOR A 0 sec 30 sec/0 9999 WRN
LOW DEW POINT SENSOR A 0 sec 30 sec/0 9999 WRN
HIGH REMOTE SENSOR 0 sec 30 sec/0 9999 WRN
POWER “A” FAILURE 0 sec 10 sec/0 9999 ALM
POWER “B” FAILURE 0 sec 10 sec/0 9999 ALM
AIRFLOW SENSOR FAILURE 0 sec 10 sec/0 9999 WRN
HUM CTRL SENSOR FAIL 0 sec 30 sec/0 9999 WRN
LOSS OF FLOW 0 sec 5 sec/0 9999 ALM
Table 4.2 Event Notification Defaults (continued)
4 Managing Events: Alarms,WarningsandMessages
86
Vertiv™ Liebert® iCOM™Installer/User Guide