NOTE: Depending on customization, some events may not be available on your cooling unit.
Event Internal delay
Default delay/Range
for adjustment
Type
MAIN FAN OVERLOAD 2 sec 5 sec/0 – 9999 * ALM
LOSS OF AIRFLOW 3 sec 3 sec/0 – 9999 * ALM
CLOGGED FILTERS 2 sec 2 sec/0 – 9999 * WRN
HIGH ROOM TEMP 1 min. after fan on 30 sec/0 – 9999 Fixed to WRN
LOW ROOM TEMP 1 min. after fan on 30 sec/0 – 9999 Fixed to WRN
HIGH ROOM HUM 1 min. after fan on 30 sec/0 – 9999 Fixed to WRN
LOW ROOM HUM 1 min. after fan on 30 sec/0 – 9999 Fixed to WRN
HIGH TEMP SENSOR A 1 min. after fan on 30 sec/0 – 9999 Fixed to WRN
LOW TEMP SENSOR A 1 min. after fan on 30 sec/0 – 9999 Fixed to WRN
HIGH HUM SENSOR A 1 min. after fan on 30 sec/0 – 9999 Fixed to WRN
LOW HUM SENSOR A 1 min. after fan on 30 sec/0 – 9999 Fixed to WRN
COMP 1 OVERLOAD Internal Calc. no ALM
COMP 2 OVERLOAD Internal Calc. no ALM
COMP 1 HIGH PRESSURE Internal Calc. no ALM
COMP 2 HIGH PRESSURE Internal Calc. no ALM
COMP 1 LOW PRESSURE Internal Calc. no ALM
COMP 2 LOW PRESSURE Internal Calc. no ALM
COMP 1 PUMPDOWN FAIL Internal Calc. no ALM
COMP 2 PUMPDOWN FAIL Internal Calc. no ALM
DIG SCROLL1 HIGH TEMP Internal Calc. no ALM
DIG SCROLL2 HIGH TEMP Internal Calc. no ALM
EL HEAT HIGH TEMP 5 sec 0 sec/0 – 9999 WRN
WORKING HRS EXCEEDED 0 sec 0 sec/0 – 9999 Fixed to WRN
SMOKE DETECTED 2 sec 2 sec/0 – 9999 * ALM
WATER UNDER FLOOR 2 sec 2 sec/0 – 9999 * ALM
COND PUMP-HIGH WATER 2 sec 2 sec/0 – 9999 * ALM
LOSS OF FLOW
5 sec
Reset delay: 10 sec
2 sec/0 – 9999 * ALM
STBY GLYCOL PUMP ON 2 sec 2 sec/0 – 9999 * ALM
STANDBY UNIT ON 2 sec 2 sec/0 – 9999 * ALM
HUMIDIFIER PROBLEM 2 sec 2 sec/0 – 9999 * ALM
NO CONNECTION w/Unit1 Internal Calc. - WRN
Table 4.2 Event Notification Defaults