ELECTRICITY
Input Description
Action
I0.0 Emergency stop switch Must be on for unit to operate
I0.1 Gate Switch
Must be on for unit to operate
I0.2 Door Closed Switches
Must be on for unit to operate
I0.3 Door Locked Switches
Must be on for unit to operate
I0.4 Low Pressure Switch
Must be on for unit to operate
I0.5 Pit Switch
Must be on for unit to operate
I0.6 Contacts of CR1
CR1 pulls in when the top nal limit switch is made.
Must be on for unit to operate.
I0.7 Overload
Must be on for unit to operate
I8.0 Slack Cable
Must be on for unit to operate
I8.1 Up contactor
Tells the PLC that the unit is running up
I8.2 Run Contactor
Tells the PLC its running
I8.3 Power failure relay
Must be on to operate in up direction
I8.4
Not Used
I8.5 Door zone sensor
Initiates the slow down when coming to a oor
I8.6 Level up sensor
Maintains the cars position at the oor
I8.7 Level down sensor
Maintains the cars position at the oor
I9.0 EZ 1 Sensor
Lights when at the rst oor, triggers EMI1 output
I9.1 EZ 2 Sensor Lights when at the second oor, triggers EMI2 output
I9.2 EZ 3 Sensor
Lights when at the third oor, triggers EMI3 output
I9.3 EZ 4 Sensor
Lights when at the fourth oor, triggers EMI4 output
I9.4 EZ 5 Sensor
Lights when at the fth oor, triggers EMI5 output
I9.5 EZ 6 Sensor
Lights when at the sixth oor, triggers EMI6 output
I9.6 First oor push button
Lights when rst oor call is made
I9.7 Second oor push button Lights when second oor call is made
I10.0 Third oor push button
Lights when third oor call is made
I10.1 Fourth oor push button
Lights when fourth oor call is made
I10.2 Fifth oor push button
Lights when fth oor call is made
I10.3 Sixth oor push button
Lights when sixth oor call is made
I10.4 Safety Pan (SCR)
Must be on for unit to operate
I10.5 Reset switch
Resets Door Fault
I10.6 SW1
Must be on to program auto gates
TROUBLESHOOTING PLC
INPUTS / OUTPUTS
SERIES : 114 , 116