Table3.4:Recommendedwiresize-Useonlycopperwire(75ºC(167°F))
PowerTerminalsWiresize
Model
Terminals
Screw
(type)
Recommended
Torque
N.m(Ibf.in)
mm²AWGTerminaltype
Power
(1)
M4
(phillips/slotted)
Fork
CFW900A04P6B2
Grounding
(2)
M4
(phillips)
1.2(10.6)2.514
Lug
Power
(1)
M4
(phillips/slotted)
Fork
CFW900A06P0B2
Grounding
(2)
M4
(phillips)
1.2(10.6)2.514
Lug
Power
(1)
M4
(phillips/slotted)
2.5/4
(3)
14/12
(3)
Fork
CFW900A07P5B2
Grounding
(2)
M4
(phillips)
1.2(10.6)
4.012Lug
Power
(1)
M4
(phillips/slotted)
2.5/6
(3)
14/10
(3)
Fork
CFW900A10P0B2
Grounding
(2)
M4
(phillips)
1.2(10.6)
6.010Lug
Power
(1)
M4
(phillips/slotted)
Fork
CFW900A04P6T2
Grounding
(2)
M4
(phillips)
1.2(10.6)2.514
Lug
Power
(1)
M4
(phillips/slotted)
Fork
CFW900A06P0T2
Grounding
(2)
M4
(phillips)
1.2(10.6)2.514
Lug
Power
(1)
M4
(phillips/slotted)
Fork
CFW900A07P5T2
Grounding
(2)
M4
(phillips)
1.2(10.6)2.514
Lug
Power
(1)
M4
(phillips/slotted)
Fork
CFW900A10P6T2
Grounding
(2)
M4
(phillips)
1.2(10.6)2.514
Lug
(1)
R/L1;S/L2;T/L3;U/T1;V/T2;W/T3;DC+;DC-.
(2)
PE.
(3)
Thefirstvalueisfor3-phasepowersupplyandmotorconnection,andthesecondvalueisforsingle-phasepowersupply.