EasyManua.ls Logo

WEG CFW900 - Fuses, Circuit Breakers and Power Supply Capacity

WEG CFW900
125 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
English
INSTALLATIONANDCONNECTION
PowerTerminalsWiresize
Model
Terminals
Screw
(type)
Recommended
Torque
N.m(Ibf.in)
mm²AWGTerminaltype
Power
(1)
M5
(pozidriv)
25.03Wireferrule
CFW900C70P0T4
Grounding
(2)
M4
(phillips)
3.7(32.8)
16.04Lug
Power
(1)
M8
(Hexagonal/Phillips
screw)
15(132.8)351Lug
CFW900D90P0T4
Grounding
(2)
M6
(Hexagonal/Phillips
screw)
5(44.2)353
Power
(1)
M8
(Hexagonal/Phillips
screw)
15(132.8)702/0Lug
CFW900D0123T4
Grounding
(2)
M6
(Hexagonal/Phillips
screw)
5(44.2)353
Power
(1)
M8
(Hexagonal/Phillips
screw)
15(132.8)703/0Lug
CFW900D0146T4
Grounding
(2)
M6
(Hexagonal/Phillips
screw)
5(44.2)353
Power
(1)
M10
(Hexagonalscrew)
30(265.5)
HD:95ou2x25
ND:95ou2x35
HD:2/0ou2x3
ND:4/0ou2x2
CFW900E0172T4
Grounding
(2)
M5eM8
(Hexagonal/Phillips
screw)
M5:3.5(31.0)
M8:15(132.8)
501/0
Lug
Power
(1)
M10
(Hexagonalscrew)
30(265.5)
HD:95ou2x35
ND:120ou2x50
HD:3/0ou2x3
ND:250ou2x1
CFW900E0200T4
Grounding
(2)
M5eM8
(Hexagonal/Phillips
screw)
M5:3.5(31.0)
M8:15(132.8)
702/0
Lug
Power
(1)
M10
(Hexagonalscrew)
30(265.5)HD:120ou
2x35
ND:2x70
HD:4/0ou2x1
ND:2x1/0
CFW900E0240T4
Grounding
(2)
M5eM8
(Hexagonal/Phillips
screw)
M5:3.5(31.0)
M8:15(132.8)
952/0
Lug
(1)
R/L1;S/L2;T/L3;U/T1;V/T2;W/T3;DC+;DC-.
(2)
PE.
3.2.3Fuses,CircuitBreakersandPowerSupplyCapacity
TheCFW900issuitableforuseincircuitswithshortcircuitcapacityofupto65kA,whichvaluevariesaccording
tothetypeofprotectionused(fuseorcircuitbreaker)andcertificationconsidered(ULorCE).Formoredetails,
seeTable3.5,Table3.6andTable3.7.
ForIECconformity,fuseswithratedcurrentandI
2
tlessthanorequaltothevaluespresentedintheTable3.5
(thistablealsopresentssuggestionsforWEGfuses)orcircuitbreakersintheinverterpowersupplyaccording
tothespecificationspresentedin
Table3.7.Whenacircuitbreakerisused,itisnecessarytoinstalltheinverter
insideametalpanelwithminimumdimensionsaccordingtothevaluesshowninTable3.7. Somemodelsof
fused-protectedinvertersalsorequiretheuseofametalpanel-formoredetailssee
Table3.5.
ForULconformity,fusesmustbeusedintheinverterpowersupplyasshowninTable3.6orcircuitbreakersin
theinverterpowersupplyasshowninTable3.7.Payattentiontotheuseofapanel,whichisrequiredforsome
invertermodelsprotectedwithfusesandforallinvertermodelsprotectedbycircuitbreaker.