English
INSTALLATIONANDCONNECTION
Table3.6:FusespecificationsasperULstandard
ProtectionwithHighSpeedFusesProtectionwith
TypeJFuses
ACPowerSupplyDCPowerSupply
Model
Maximum
Short-CircuitCurrent
ofthePowerSupply[kA]
Panel
FuseRated
Current
[A]
FuseRated
Current
[A]
Fuse
Recommendation
FuseRated
Current
[A]
Fuse
Recommendation
CFW900A04P6B2--35MersenA70QS35-4
CFW900A06P0B2--35MersenA70QS35-4
CFW900A07P5B2--35MersenA70QS35-4
CFW900A10P0B2--35MersenA70QS35-4
CFW900A04P6T2--35MersenA70QS35-4
CFW900A06P0T2--35MersenA70QS35-4
CFW900A07P5T2--35MersenA70QS35-4
CFW900A10P6T2--35MersenA70QS35-4
CFW900A13P0T2--35MersenA70QS35-4
CFW900A19P0T2
Any
typeJ≤40A
--35MersenA70QS35-4
CFW900B26P0T2--80MersenA70QS80-4
CFW900B34P0T2--80MersenA70QS80-4
CFW900B45P0T2
5No
Any
typeJ≤90A
--80MersenA70QS80-4
CFW900C56P0T2-80MersenA100P80-4150MersenA70QS150-4
CFW900C70P0T2-100MersenA100P100-4150MersenA70QS150-4
CFW900C80P0T2
Yes
(1)
-150MersenA100P150-4150MersenA70QS150-4
CFW900D0110T2-125MersenA100P125-4250MersenA70QS250-4
CFW900D0135T2-200MersenA100P200-4250MersenA70QS250-4
CFW900D0150T2
Yes
(1)
-250MersenA100P250-4250MersenA70QS250-4
CFW900E0172T2--400MersenA70QS400-4
CFW900E0195T2--400MersenA70QS400-4
CFW900E0250T2
10
Yes
(2)
Any
typeJ≤450A
--400MersenA70QS400-4
CFW900A02P8T4--35MersenA70QS35-4
CFW900A03P6T4--35MersenA70QS35-4
CFW900A04P8T4--35MersenA70QS35-4
CFW900A06P5T4--35MersenA70QS35-4
CFW900A09P6T4--35MersenA70QS35-4
CFW900A14P0T4--35MersenA70QS35-4
CFW900A17P0T4
Any
typeJ≤40A
--35MersenA70QS35-4
CFW900B26P0T4--80MersenA70QS80-4
CFW900B33P0T4--80MersenA70QS80-4
CFW900B39P0T4
5No
Any
typeJ≤90A
--80MersenA70QS80-4
CFW900C50P0T4-60MersenA100P60-4150MersenA70QS150-4
CFW900C62P0T4-80MersenA100P80-4150MersenA70QS150-4
CFW900C74P0T4
Yes
(1)
-150MersenA100P150-4150MersenA70QS150-4
CFW900D96P0T4-125MersenA100P125-4250MersenA70QS250-4
CFW900D0124T4-150MersenA100P150-4250MersenA70QS250-4
CFW900D0146T4
Yes
(1)
-250MersenA100P250-4250MersenA70QS250-4
CFW900E0172T4--400MersenA70QS400-4
CFW900E0203T4--400MersenA70QS400-4
CFW900E0242T4
10
Yes
(2)
Any
typeJ≤450A
--400MersenA70QS400-4
(1)
Panelwithaminimumsizeof1.5timesthesizeoftheinverter.
(2)
Minimumpaneldimensions(widthxheightxdepth):600x1000x600mm(23.6x39.3x23.6in).