SSW7000 | 6-1
Internal Connections
6 INTERNAL CONNECTIONS
6.1. SSW7000 ELECTRONIC BOARDS
The SSW7000 is supplied with the versions of electronic boards 2 (V2) and 3 (V3). The both versions use the
same source board (FSMT), but with different firmware. The version 3 was developed to attend the electrical
isolation class required for the SSW7000 of 13.8kV. The two versions of electronic boards operate with voltage
supply at 110/220Vac (automatic selection).
Table 6.1: Versions of electronic boards SSW7000
Version 2
Version 3
SSW7000A 2.3/4.16/6.9kV
(110V/220V)
SSW7000C 2.3/4.16kV
(110/220V)
SSW7000C 6.9kV
(110/220V)
SSW7000C 13.8kV
(110/220V)
Name
Description
Name
Description
Name
Description
Name
Description
CC11
Control board C1
interface with
the user
CC11
Control board C1
interface with the
user
CC11
Control board C1
interface with
the user
CC11
Control board C1
interface with the
user
CSM2.00
Control board C2
medium voltage
control for 2.3 kV
CSM2.00
Control board C2
medium voltage
control for 2.3 kV
CSM3.02
Control board C2
medium voltage
control for 6.9 kV
CSM3.03
Control board C2
medium voltage
control for 13.8 kV
CSM2.01
Control board C2
medium voltage
control for 4.16
kV
CSM2.01
Control board C2
medium voltage
control for 4.16 kV
FSMT.01
Power supply of
board CC11,
fixed relay
outputs
FSMT.01
Power supply of
board CC11, fixed
relay outputs
CSM2.02
Control board C2
medium voltage
control for 6.9 kV
FSMT.00
Power supply of
board CC11, fixed
relay outputs
GDSMC2.00
Gate driver
without
temperature
measurement
GDSMC2.02
Gate driver with
temperature
measurement
FSMT.00
Power supply of
board CC11,
fixed relay outputs
GDSMC.00
Gate driver with
temperature
measurement
GDSMC2.01
Gate driver
without
temperature
measurement
GDSMC2.03
Gate driver without
temperature
measurement
GD1SM Upper gate driver GDSMC.01
Gate driver without
temperature
measurement
CSMGA.00
Auxiliary board with
gate signal
GD2SM Lower gate driver CSMAT.00
Auxiliary board for
voltage attenuation
Note. In the CSM board is connected a specific toroidal transformer for each version of electronic boards.
6.1.1. CC11 Board
Table 6.2: Description of the CC11board connectors
Terminal Strip
Description
XC1 User connections
1 a 29
Refer to the item 5.2.10. - User Signal and Control Connections
SLOT
User connections
1
Accessory for the motor temperature measurement
2
3
Communication accessories
4
Anybus-CC communication accessories
5
Flash memory
Interface
User connections
XC20
USB
XC21
HMI
CC11 FSM Connections between boards
XC60
XC1
Signals and CC11 feeding

Table of Contents

Other manuals for WEG SSW7000