35Manual maxGUARD2526740000/02/03.2018
6 Electronicloadmonitors | AMG ELM-x...
Technical data AMG ELM 6... AMG ELM 12...
General
Rated voltage
24VDC
Operational voltage range
18–30VDC
Low voltage detection
Yes (supply voltage<18VDC)
Surge detection
Yes (supply voltage>31.2VDC)
Rated output current I
OUT,rated
6A 12A
Current consumption
I
OUT
+30mA
VoltagedropatI
OUT,rated
200mV 250mV
Capacitive load
15,000 µF 20,000 µF
Overtemperature protection
Yes
Width
6.1mm 12.2mm
Tripping characteristic
Adjustable
Yes
Tripping current I
T
1A, 2A, 3A, 4A, 6A 4A, 6A, 8A, 10A, 12A
Characteristics(normal)
1A
N
, 2A
N
, 3A
N
, 4A
N
, 6A
N
4A
N
, 6A
N
, 8A
N
, 10A
N
, 12A
N
Characteristics(delayed)
1A
T
2A
T
3A
T
, 4A
T
, 6A
T
4A
T
6A
T
8A
T
, 10A
T
, 12A
T
Bus decoupling, bus coupling
Alarm(tripped,fault)
Yes
Overload advance warning
Yes
Reset
Yes
ON/OFF
Yes
Button function
Reset
Yes
ON/OFF
Yes