39Manual maxGUARD2526740000/02/03.2018
6 Electronicloadmonitors | AMGELM-xF CL2
Technical data AMGELM-1FCL2 AMGELM-2FCL2 AMGELM-4FCL2
General
Rated voltage
24VDC
Operational voltage range
18...30VDC
Low voltage detection
Yes (supply voltage<18VDC)
Surge detection
Yes (supply voltage>31,2VDC)
Rated output current I
OUT,rated
1A 2A 4A
Current consumption
I
OUT
+30mA
VoltagedropatI
OUT,rated
200mV
Capacitive load
4 700µF
Overtemperature protection
No
Width
6,1mm
Tripping behaviour
Adjustable
No
Tripping current I
T
1A 2A 4A
Characteristics(normal)
1A
CL2
2A
CL2
4A
CL2
Characteristics(delayed)
No
Bus decoupling, bus coupling
Alarm(tripped,fault)
Yes
Overload advance warning
(I>90%)
No
Reset
Yes
ON/OFF
Yes
Button function
Reset
Yes
ON/OFF
Yes