Diagnostic & Troubleshooting 6 - 6
OL3
Overtorque Det 1
Overtorque Detection 1
Drive output current > L6-02 for more than
the time set in L6-03
Motor is overloaded
Ensure the values in L6-02 and
L6-03 are appropriate
Check application/machine
status to eliminate fault
OPR
Oper Disconnect
Digital Operator Connection Fault
The Drive will stop if the digital operator is
removed when the Drive is commanded to
run through the digital operator
The digital operator is not
attached or the digital opera-
tor connector is broken
Attach the digital operator
Check the digital operator
connector
Verify the setting of o2-06
OV
DC Bus Overvolt
DC Bus Overvoltage
208-240Vac: Trip point is 400Vdc
480Vac: Trip point is 800Vdc
High input voltage at R/L1,
S/L2 and T/L3
Check the input circuit and
reduce the input power to within
specifications
The deceleration time is set
too short
Extend the time in C1-02
Power factor correction
capacitors are being used on
the input to the Drive
Remove the power factor
correction capacitors
PF
Input Pha Loss
Input Phase Loss
Drive input power supply has an open phase
or has a large imbalance of input voltage
Open phase on the input of the
Drive
Check the input voltage
Loose terminal screws at
R/L1, S/L2 or T/L3.
Tighten the terminal screws
Momentary power loss
occurred
Check the input voltage
Input voltage fluctuation too
large
Check the input voltage
Parameter L8-06 value is set
incorrectly
Adjust L8-06 according to your
application. The higher the value
the less sensitive it becomes.
PUF
DC Bus Fuse Open
DC Bus Fuse
Detects if the DC bus fuse has opened
Shorted output transistor(s) or
terminals
Remove power from the Drive
Disconnect the motor
Perform the checks without
power in Table 6.6
Replace the shorted component(s)
Replace the defective fuse
RH
DynBrk Resistor
Dynamic Braking Resistor
The protection of the dynamic braking
resistor based on setting of L8-01
Overhauling load, extended
dynamic braking duty cycle,
defective dynamic braking
resistor
Verify dynamic braking duty
cycle
Monitor DC bus voltage
Replace dynamic braking
resistor
Table 6.1 Fault Displays and Processing
Digital
Operator Display
Description Cause Corrective Action

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA E7 Drive and is the answer not in the manual?

YASKAWA E7 Drive Specifications

General IconGeneral
BrandYASKAWA
ModelE7 Drive
CategoryController
LanguageEnglish

Related product manuals