EasyManuals Logo

YASKAWA E7 Drive User Manual

YASKAWA E7 Drive
204 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #134 background imageLoading...
Page #134 background image
Parameter List A - 2
Table 1: E7 Parameter List
Parameter
No.
Parameter Name
Digital Operator Display
Description
Setting
Range
Factory
Setting
Menu
Location
Initialization
A1-00
Language Selection
Select Language
Language selection for digital operator display
0: English
1: Japanese
2: Deutsch
3: Francais
4: Italiano
5: Espanol
6: Portugues
*Not returned to factory setting by initialization
0 to 6 0 Quick Setting
A1-01
Access Level Selection
Access Level
This setting determines which parameters are accessable.
0: Operation Only
1: User Level
2: Advanced Level
0 to 2 2 Programming
A1-03
Initialize Parameters
Init Parameters
Used to return all parameters to their factory or user setting.
0: No Initialize
1110: User Initialize (The user must set their own parameter
default values and then parameter o2-03 must be set to “1” to save
them. If the parameter values are changed after o2-03 is set to “1”,
the user default values can be restored by setting A1-03 to 1110.)
2220: 2-Wire Initial
3330: 3-Wire Initial
0 to
3330
0 Programming
A1-04
Password 1
Enter Password
When the value set into A1-04 does NOT match the value set into
A1-05, parameters A1-01 thru A1-03 and A2-01 thru A2-32 cannot
be changed. All other parameters as determined by A1-01 can be
changed. Parameter A1-05 can be accessed by pressing the MENU
key while holding the RESET key.
0 to 9999 0 Programming
A1-05
Password 2
Select Password
0 to 9999 0 Programming
User Parameters
A2-01
User Parameter 1
User Param 1
Selects the parameters to be available in the User Access Level
(A1-01 = 1). These are the only parameters accessible for the user
level. These parameters are not related to the User Initialize
function.
b1-01
to
o3-02
Programming
A2-02
User Parameter 2
User Param 2
Programming
A2-03
User Parameter 3
User Param 3
Programming
A2-04
User Parameter 4
User Param 4
Programming
A2-05
User Parameter 5
User Param 5
Programming
A2-06
User Parameter 6
User Param 6
Programming
Denotes that parameter can be changed when the drive is running.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA E7 Drive and is the answer not in the manual?

YASKAWA E7 Drive Specifications

General IconGeneral
BrandYASKAWA
ModelE7 Drive
CategoryController
LanguageEnglish

Related product manuals