Electrical Installation 2 - 4
2037
R/L1, S/L2, T/L3, , 1 U/T1,
V/T2, W/T3, R1/L11, S1/L21, T1/L31
M10
154.8 to 197.9
(17.6 to 22.5)
2/0 to 4/0
(60 to 100)
2/0
(60)
600Vac
UL-type
vinyl-sheathed
or equivalent
3
M8
77.4 to 95.0
(8.8 to 10.8)
10 to 4
(5.5 to 22)
–
M10
154.8 to 197.9
(17.6 to 22.5)
2 to 2/0
(30 to 60)
2
(30)
r/
l1, s/l2
M4
11.4 to 12.3
(1.3 to 1.4)
20 to 10
(0.5 to 5.5)
16
(1.25)
2045
R/L1, S/L2, T/L3, , 1 U/T1,
V/T2, W/T3, R1/L11, S1/L21, T1/L31
M10
154.8 to 197.9
(17.6 to 22.5)
3/0 to 4/0
(80 to 100)
3/0
(80)
3
M8
77.4 to 95.0
(8.8 to 10.8)
10 to 4
(5.5 to 22)
–
M10
154.8 to 197.9
(17.6 to 22.5)
1 to 2/0
(38 to 60)
1
(38)
r/
l1, s/l2
M4
11.4 to 12.3
(1.3 to 1.4)
20 to 10
(0.5 to 5.5)
16
(1.25)
2055
R/L1, S/L2, T/L3, , 1
M12
276.2 to 344.8
(31.4 to 39.2)
1/0 to 4/0
(50 to 100)
1/0 X 2P
(50 X 2P)
U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L31 M10
154.8 to 197.9
(17.6 to 22.5)
4/0
(100)
4/0
(100)
3
M8
77.4 to 95.0
(8.8 to 10.8)
10 to 2/0
(5.5 to 60)
–
M10
154.8 to 197.9
(17.6 to 22.5)
3 to 4/0
(30 to 60)
1/0
(50)
r/
l1, s/l2
M4
11.4 to 12.3
(1.3 to 1.4)
20 to 10
(0.5 to 5.5)
16
(1.25)
2075
R/L1, S/L2, T/L3, , 1
M12
276.2 to 344.8
(31.4 to 39.2)
3/0 to 250
(80 to 125)
3/0 X 2P
(80 X 2P)
U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L31 M10
154.8 to 197.9
(17.6 to 22.5)
3/0 to 4/0
(80 to 100)
3/0 X 2P
(80 X 2P)
3
M8
77.4 to 95.0
(8.8 to 10.8)
10 to 2/0
(5.5 to 60)
–
M10
154.8 to 197.9
(17.6 to 22.5)
3/0 to 400
(100 to 200)
3/0
(100)
r/
l1, s/l2
M4
11.4 to 12.3
(1.3 to 1.4)
20 to 10
(0.5 to 5.5)
16
(1.25)
2090
R/L1, S/L2, T/L3, , 1
M12
276.2 to 344.8
(31.4 to 39.2)
250 to 400
(150 to 200)
250 X 2P
(150 X 2P)
U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L31 M12
276.2 to 344.8
(31.4 to 39.2)
4/0 to 300
(100 to 150)
4/0 X 2P
( 100 X 2P)
3
M8
77.4 to 95.0
(8.8 to 10.8)
10 to 2/0
(5.5 to 60)
–
M12
276.2 to 344.8
(31.4 to 39.2)
2/0 to 300
(60 to 150)
2/0 X 2P
(60 X 2P)
r/
l1, s/l2
M4
11.4 to 12.3
(1.3 to 1.4)
20 to 10
(0.5 to 5.5)
16
(1.25)
2110
R/L1, S/L2, T/L3, , 1
M12
276.2 to 344.8
(31.4 to 39.2)
350 to 600
(200 to 325)
350 X 2P, or 1/0
X 2P (200 X 2P,
or 50 X 4P)
U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L31 M12
276.2 to 344.8
(31.4 to 39.2)
150 to 325
(300 to 600)
300 X 2P,or 1/0 X
4P (150 X 2P, or
1/0 X4P)
3
M8
77.4 to 95.0
(8.8 to 10.8)
10 to 2/0
(5.5 to 60)
–
M12
276.2 to 344.8
(31.4 to 39.2)
300
(150)
300 X 2P
(150 X 2P)
r/
l1, s/l2
M4
11.4 to 12.3
(1.3 to 1.4)
20 to 10
(0.5 to 5.5)
16
(1.25)
*Use 75°C copper wire or equivalent
Table 2.1 208-240Vac Wire Sizes and Connector Specifications
Drive Model
CIMR-E7U
Terminal Symbol
Ter m i nal
Screws
Clamping
To r q u e
lb. in.
(N•m)
Wire Size
Range
AWG
(mm
2
)
Recommended
Wire Size
AWG
(mm
2
)
Wire
Type