n006
Reverse LED LCD
Prohibit Setting
Setting
0 REV Allowed ** 0 or 1 0
(Reverse Oper)
1 REVProhibited
n007
LOCAL/ LED LCD
REMOTE Setting
Setting
0 Disabled 0 or 1 1
Key Function 1 Enabled **
(Local/Remote
Key)
n008
STOP KEY LED LCD
Function Setting
Setting Description
0 Disabled STOP key is effective only 0 or 1 1
(Oper STOP when sequence command
Key) (per
n002
) is to be from
Digital Operator
1 Enabled ** STOP key is effective-
regardless of programming
of
n002
n009
Frequency LED LCD
Reference Setting
Setting Description
Setting Method 0 Enter Not Used ENTER key does not 0 or 1 1
From Digital have to be pressed to
Operator write-in new value
1 Enter Key ENTER key must be
(Operator Used ** pressed to write-in
M.O.P.) new value
n010
V/f Pattern LED LCD
Selection Setting
Setting Description
0 User Defined V/f Custom V/f pattern 0 or 1 1 5.28
(V/f Selection) (60 Hz VT default)
See Note 5 1 60 Hz Preset ** Preset V/f pattern
n011
Frequency – Maximum level for drive output frequency 50.0 to 400.0 60.0 (Hz) 5.28
Max.
See Note 1
(Max
Frequency)
n012
Voltage – Max. Maximum level of drive output voltage 0.1 to 255.0 230.0 (VAC) 5.28
(230V drive) See Note 1
(Max Voltage) 0.1 to 510.0 460.0 (VAC)
(460V drive) See Note 1
0.1 to 733.1 575.0 (VAC)
(600V drive) See Note 1
n013
Frequency – Level of frequency at which drive 0.2 to 400.0 60.0 (Hz) 5.28
Max. Voltage output voltage will reach
n012
value See Note 1
Point
(Base
Frequency)
Table A1-1. Drive Parameters (
nXXX
) – Continued
PARAM.
FUNCTION NAME SETTING FACTORY USER PARA.
NO. (ACTUAL DISPLAY)
DESCRIPTION
RANGE SETTING ** SETTING REF.