n082
DB Resistor LED LCD 0 or 1 0
Overheat Setting
Setting Description
Function (rH) 0 Disabled ** No DB protection calculated
or provided
(DB Resistor 1 Enabled Protection provided for
Prot) installed factory option
DB resistor
n083
Input Phase 1 to 100 7 (%) 5.29
Loss Detection When set to 100%, input phase
Level (SPi) loss detection is disabled
(In Ph Loss Lvl)
n084
PID Selection LED LCD
Setting
Setting Description
(PID Mode) 0 Disabled ** PID disabled 0 to 3 0 5.22A
1 Enabled D=Fdbk PID enabled
See Note 5 2 Enabled D=Fdfwd PI with Feed Forward
3 Enabled RevFdbk Inverted PID
n085
Feedback 0.00 to 10.00 1.00 5.22E
Calibration
Gain
(PID Fdbk Gain)
n086
Proportional 0.0 to 10.0 1.0 5.22G
Gain
(PID P Gain)
n087
Integral Gain 0.0 to 100.0 10.0 (Sec) 5.22G
(PID I Time)
n088
Derivative 0.00 to 1.00 0.00 (Sec) 5.22G
Time
(PID D Time)
n089
Limit of Integral 0 to 109 100 (%) 5.22H
Value
(PID I Limit)
n090
Feedback Loss LED LCD
Detection Setting
Setting Description
0 Disabled ** Detection is disabled 0 or 1 0 5.22F
(PID FdbkLoss 1 MF Output Only Detection is enabled
Sel) - alarm only
2 Fault output Detection is enabled - fault
n091
Feedback Loss 0 to 100 0 (%) 5.22F
Det. Level
(PID FdbkLoss
Lvl)
Table A1-1. Drive Parameters (
nXXX
) – Continued
PARAM.
FUNCTION NAME SETTING FACTORY USER PARA.
NO. (ACTUAL DISPLAY)
DESCRIPTION
RANGE SETTING ** SETTING REF.