n102
Stop Method LED LCD 0 to 3 1 5.16
on Modbus Setting
Setting Stop method
Communication 0
Ramp STOP/Decel1
Ramp to stop – Decel 1
Error (CE) (fault)
1
Coast to STOP**
Coast to stop (fault)
(MODBUS 2
Ramp STOP/Decel2
Ramp to stop – Decel 2
FaultStop) (fault)
3 Continue Oper Continue operation
(alarm)
n103
Modbus LED LCD 0 to 3 0 5.16
Setting Setting
Setting Stop method
Frequency 0 1 = 0.1Hz ** 0.1 Hz / 1
Reference Unit 1 1 = 0.01Hz 0.01 Hz / 1
(MODBUS 2 30000 = 100% 100% / 30000
Fref Unit) 3 1 = 0.1% 0.01 % / 1
n104
Modbus Slave 0 to 31 1 5.16
Address
(MODBUS
Address)
n105
Modus BPS LED LCD 0 to 2 2 5.16
Selection Setting
Setting
0 2400 Baud
(MODBUS 1 4800 Baud
Baud Rate) 2 9600 Baud **
n106
Modbus Parity LED LCD 0 to 2 0 5.16
Selection Setting
Setting
0 No parity **
(MODBUS 1 Even parity
Parity) 2 Odd parity
n107
Slip 0.0 to 9.9 0.0 (%) 5.23.1
Compensation
Gain
(Slip Comp
Gain)
n108
Motor No-load 0 to 99 30 (%) 5.23.1
Current
(Mtr No-Load
Amp)
n109
Slip Comp. 0.0 to 25.5 2.0 (Sec) 5.23.1
Primary Delay
Time Constant
(Slip Comp
Delay)
Table A1-1. Drive Parameters (
nXXX
) – Continued
PARAM.
FUNCTION NAME SETTING FACTORY USER PARA.
NO. (ACTUAL DISPLAY)
DESCRIPTION
RANGE SETTING ** SETTING REF.
A1-14