A6-6
5. The Braking Transistor Unit and Remote Mount Resistor Unit MUST BE GROUNDED.
Observe the following precautions:
• Ground units per local electrical codes.
• If the installation requires the Remote Mount Resistor Unit to be used without its
enclosure (with grounding terminal), ground it by attaching a ground lead
at one of the mounting screws.
• Grounding resistance of the Braking Transistor Unit should be 100 ohms or less.
(1)
Fuse required only if UL/CUL certification is needed. See separate instruction sheet
02Y00025-0393 for details.
Figure A6-4. Wiring Single Braking Transistor Unit and Remote Mount Resistor Unit to Drive
(GPD506V-A054 and -A068 [CIMR-P5M20111F and 20151F], -B380 [CIMR-P5M41850F],
and CIMR-P5M50301F thru 50371F).