Motor Rated FLA — Motor Rated Current [ n033 ]
Sets the Amps used for detecting motor overload. This is
normally set to the motor rated current value (nameplate full-load
amps). When set to " 0.0 ", motor overload protection is
disabled. The factory settings are listed in Appendix 1.
PID Mode — PID Selection [ n084 ]
Setting data to "Disabled" (" 0 ") (factory setting) disables the
PID function. Setting to "Enabled D = Fdbk" (" 1 ") enables PID;
setting to "Enabled D = Fdfwd" (" 2 ") enables the "Feed
Forward" function; setting to "Enabled RevFdbk" (" 3 ") enables
the "Inverted PID" function. See "PID Control", paragraph 5.22.
Energy Save Sel — Energy Saving Selection [ n096 ]
Setting data to "Disabled" (" 0 ") (factory setting) disables the
energy saving function; and setting to "Enabled" (" 1 ") enables
this function. See “Energy Saving Control”, paragraph 5.9.
Parameter nXXX — Parameter Programming
Selects or reads data using parameter number (nXXX ). Data is
displayed by pressing the ENTER key, and can be changed by
pressing the “up arrow” or “down arrow” keys. Any changes can
be saved by again pressing the ENTER key. Pressing the DSPL
key exits the Programming mode.
4-4