0 Reverse RUN (2W) Reverse Run/Stop command (for MUST BE SET ONLY IN n036.
2-wire control) Redefines terminals:
S1 = Run/Stop Forward;
S2 = Run/Stop Reverse
1 FWD/REV Cmd (3W) FWD/REV selection (for MUST BE SET ONLY IN n036.
3-wire control) Redefines terminals:
S1 = Run; S2 = Stop;
S3 = FWD/REV select
2 Ext Fault (NO) External fault (N.O. contact input) Drive trips; Digital Operator displays
" EFX ", where X is 2-6, corresponding
to the terminal S2-S6, which is
3 Ext Fault (NC) External fault (N.C. contact input) receiving the fault input signal
4 Fault Reset Fault Reset Resets fault, only if RUN command is
not present
5 LOC/REM Sel Remote/Local selection Open = Operates according to setting
of n002
Closed = Operates from keys of the
Digital Operator
See paragraph 5.19A
6 COM/INV Sel GPD Drive operation & reference/ Open = Operates according to setting
serial communication selection of n002
Closed = Operates from serial
communication
See paragraph 5.16
7
STOP Cmd/Dec 2 NO
Quick Stop Open = Stop according to setting of
(N.O. Contact Input) n004
Closed = Ramp to stop by Decel Time 2
(n021)
8
STOP Cmd/Dec 2 NC
Quick Stop (N.C. contact input) Open = Ramp to stop by Decel Time 2
(n021)
Closed = Stop according to setting of
n004
9 Master FREF Sel Auto/Manual frequency If n043= "FV=MSTR FI=Aux" ("0")
reference selection Open = Frequency reference from
terminal FV
Closed = Frequency reference from
terminal FI
If n043= "FV=Aux FI=MSTR" ("1")
Open = Frequency reference from
terminal FI
Closed = Frequency reference from
terminal FV
10 Multi-Step Spd 1 Multi-step frequency ref. select 1
11 Multi-Step Spd 2 Multi-step frequency ref. select 2 See paragraph 5.19B
12 Multi-Step Spd 3 Multi-step frequency ref. select 3
13 JOG Command Jog selection Closed = Jog selected
See paragraph 5.15
5-29
Continued
LED LCD
SETTING SETTING FUNCTION DESCRIPTION **
Table 5-2. n036 thru n040 Data Settings
5.19 MULTI-FUNCTION INPUT TERMINALS (Term. S2-S6)