Parameter List
7
7.8 H: Terminal Functions
YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup 205
Setting Value Function Description
19F !High PI Auxiliary Control
Level
The terminal deactivates when the PI Aux Feedback Level is more than YF-12 [PI Aux Control High Level Detect] or if the drive
detects an HIAUX [High PI Aux Feedback Level] fault.
1A9 !RELAY Operator Control
The terminal changes to OFF or ON when you push the RELAY ( ) button. When the terminal is ON, push to turn
it OFF. When the terminal is OFF, push to turn in ON.
1AB !Thrust Mode The terminal deactivates when the output frequency is between 0.0 Hz and the value set in Y4-12 [Thrust Frequency] and the Thrust
Bearing function is active.
1AC !Setpoint Not Maintained The terminal deactivates when the drive detects NMS [Setpoint Not Met] condition.
1B2 !BAS Interlock The terminal deactivates when the Run command is active or the drive is outputting the voltage. The drive will use this as an
actuation signal for an external damper.
1B8 !Pump Fault The terminal deactivates when one of these faults is active: LFB [Low Feedback Sensed], HFB [High Feedback Sensed], NMS
[Setpoint Not Met], or EFx [External Fault (Terminal Sx)].
1B9 !Transducer Loss The terminal deactivates when the current into the analog input associated with PID feedback is more than 21 mA or less than 3
mA, or an FDBKL [WIRE Break] Fault or an FDBKL [Feedback Loss Wire Break] Alarm is active.
1BA !PI Auxiliary Control Active The terminal deactivates when the PI Auxiliary Controller has an effect on the output speed.
1BB !Differential Feedback
Exceeded
The terminal deactivates when the difference between the PID Feedback and the value from the terminal set for H3-xx = 2D
[Differential Feedback] is more than Y4-18 [Differential Level] for the time set in Y4-19 [Differential Lvl Detection Time].
1BC !Sleep Active The terminal deactivates when the Sleep function is active and the drive is not operating.
Note:
The terminal will not deactivate for Sleep Boost function.
1BD
!Start Delay The terminal deactivates when the Feedback is more than the start level or the Feedback is less than the Inverse PID and the start
timer is timing.
Note:
You must set Y1-04 [Sleep Wake-up Level] ≠ 0 and Y1-05 [Sleep Wake-up Level Delay Time] ≠ 0 to use this function.
1BE
!Pre-Charge The terminal deactivates when the drive is in Pre-Charge Mode.
1C0 !HAND Mode The terminal deactivates when the drive is in HAND Mode operation.
1C1 !AUTO Mode The terminal deactivates when the drive is in AUTO Mode operation.
1C2 !OFF Mode The terminal deactivates when the drive is in OFF Mode operation.
1C3 !Main Feedback Lost The terminal deactivates when the drive loses the main PID feedback.
1C4 !Backup Feedback Lost The terminal deactivates when the drive loses the backup PID feedback.
â—† H3: Analog Inputs
No.
(Hex.)
Name Description
Default
(Range)
H3-01
(0410)
Terminal A1 Signal Level
Select
Sets the input signal level for MFAI terminal A1.
0 : 0 to 10V (Lower Limit at 0)
2 : 4 to 20 mA
3 : 0 to 20 mA
0
(0 - 3)
H3-02
(0434)
Terminal A1 Function
Selection
Sets the function for MFAI terminal A1. 0
(0 - 31)
H3-03
(0411)
RUN
Terminal A1 Gain Setting Sets the gain of the analog signal input to MFAI terminal A1. 100.0%
(-999.9 - +999.9%)
H3-04
(0412)
RUN
Terminal A1 Bias Setting Sets the bias of the analog signal input to MFAI terminal A1. 0.0%
(-999.9 - +999.9%)
H3-09
(0417)
Terminal A2 Signal Level
Select
Sets the input signal level for MFAI terminal A2.
0 : 0-10V (LowLim=0)
2 : 4 to 20 mA
3 : 0 to 20 mA
2
(0 - 3)
H3-10
(0418)
Terminal A2 Function
Selection
Sets the function for MFAI terminal A2.
Note:
The default setting for H3-10 changes when b5-01 [PID Mode Setting] changes:
• b5-01 = 0 [Disabled]: 0
• b5-01 ≠ 0: B
Determined by b5-01
(0 - 31)