Parameter List
7
7.9 L: Protection Functions
YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup 217
No.
(Hex.)
Name Description
Default
(Range)
L8-07
(04B3)
Output Phase Loss
Protection Sel
Sets the function to enable and disable output phase loss detection. The drive starts output phase loss
detection when the output current decreases to less than 5% of the drive rated current.
Note:
The drive can incorrectly start output phase loss detection when te motor rated current is very
small compared to the drive rating.
0 : Disabled
1 : Fault when one phase is lost
2 : Fault when two phases are lost
1
L8-09
(04B5)
Output Ground Fault
Detection
Sets the function to enable and disable ground fault protection.
0 : Disabled
1 : Enabled
Determined by o2-04
(0, 1)
L8-10
(04B6)
Heatsink Fan Operation
Selection
Sets operation of the heatsink cooling fan.
0 : During Run, w/ L8-11 Off-Delay
1 : Always On
2 : On when Drive Temp Reaches L8-64
0
(0 - 2)
L8-11
(04B7)
Heatsink Fan Off-Delay
Time
Sets the length of time that the drive will wait before it stops the cooling fan after it cancels the Run
command when L8-10 = 0 [Heatsink Fan Operation Selection = During Run, w/ L8-11 Off-Delay].
300 s
(0 - 300 s)
L8-12
(04B8)
Ambient Temperature
Setting
Sets the ambient temperature of the drive installation area.
Note:
The setting range changes when the L8-35 [Installation Method Selection] setting changes.
• When L8-35 = 0 or 2 [IP20/UL Open Type or IP20/UL Type 1]: -10 °C~+60 °C
• When L8-35 = 1 or 3 [Side-by-Side Mounting or IP55/UL Type 12]: -10 °C~+50 °C
40 °C
(Determined by L8-35)
L8-15
(04BB)
Drive oL2 @ Low Speed
Protection
Sets the function to decrease drive overload at low speeds to prevent damage to the main circuit
transistor during low speed operation (at 6 Hz or slower) to prevent oL2 [Drive Overloaded].
Note:
Contact Yaskawa or your nearest sales representative before disabling this function at low
speeds. If you frequently operate drives with high output current in low speed ranges, it can cause
heat stress and decrease the life span of drive IGBTs.
0 : Disabled (No Additional Derate)
1 : Enabled (Reduced oL2 Level)
1
(0, 1)
L8-18
(04BE)
Software Current Limit
Selection
Set the software current limit selection function to prevent damage to the main circuit transistor
caused by too much current.
0 : Disabled
1 : Enabled
0
(0, 1)
L8-19
(04BF)
Freq Reduction @ oH Pre-
Alarm
Sets the ratio at which the drive derates the frequency reference during an oH alarm. 20.0%
(10.0 - 100.0%)
L8-35
(04EC)
Installation Method
Selection
Sets the type of drive installation.
0 : IP20/UL Open Type
1 : Side-by-Side Mounting
2 : IP20/UL Type 1
3 : IP55/UL Type 12
2
(0 - 3)
L8-38
(04EF)
Carrier Frequency Reduction Sets the carrier frequency reduction function. The drive decreases the carrier frequency when the
output current is more than a specified level.
1 : Enabled below 6 Hz
2 : Enabled for All Speeds
3 : Enable at Overload
Determined by o2-04
(1 - 3)
L8-41
(04F2)
High Current Alarm
Selection
Sets the function to cause an HCA [High Current Alarm] when the output current is more than 150%
of the drive rated current.
0 : Disabled
1 : Enabled
0
(0, 1)
L8-97
(3104)
Carrier Freq Reduce during
OH
Sets the function to decrease carrier frequency during oH pre-alarm.
0 : Disabled
1 : Enabled
0
(0, 1)
â—† L9: Drive Protection 2
No.
(Hex.)
Name Description
Default
(Range)
L9-16
(11DC)
Expert
FAn1 Detect Time Sets the detection time for FAn1 [Drive Cooling Fan Fault]. Yaskawa recommends that you do not
change this parameter value.
4.0 s
(0.0 - 30.0 s)