7.12 S: Special Applications
232 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
No.
(Hex.)
Name Description
Default
(Range)
S6-11
(3242)
Expert
EMOVR Drive Protection
Fault ON
Sets the bit to enable fault detection during Emergency Override.
bit 0 : Uv1 - DC Bus Undervoltage
bit 1 : CoF - Current Offset Fault
bit 2 : Reserved
bit 3 : Err - EEPROM Write Error
bit 4 : Reserved
bit 5 : Reserved
bit 6 : oL2 - Drive Overload
bit 7 : oPr - Operator Connection
bit 8 : PF - Input Phase Loss
bit 9 : Reserved
bit 10 : Reserved
bit 11 : oH - Heatsink Overheat
bit 12 : oH1 - Heatsink Overheat
bit 13 : OD - Output Disconnect
bit 14 : FAn1 - Cooling Fan Fault
bit 15 : ov2 - DC Bus Overvoltage 2
Note:
The drive sets the bits in Hex.
0
(0 - FFFF)
S6-12
(3243)
Expert
EMOVR Motor Protection
Fault ON
Sets the bit to enable fault detection during Emergency Override.
bit 0 : LF - Output Phase Loss
bit 1 : LF2 - Output Current Imbalance
bit 2 : oH3 - Motor Overheat PTC Input
bit 3 : oH4 - Motor Overheat PTC Input
bit 4 : Reserved
bit 5 : oL1 - Motor Overload
bit 6 : oL3 - Overtorque Detection 1
bit 7 : oL4 - Overtorque Detection 2
bit 8 : oL7 - High Slip Braking Overload
bit 9 : Reserved
bit 10 : UL3 - Undertorque Detection 1
bit 11 : UL4 - Undertorque Detection 2
bit 12 : UL6 - Motor Underload
bit 13 : Reserved
bit 14 : oS - Overspeed
bit 15 : dEv: Speed Deviation
Note:
The drive sets the bits in Hex.
0
(0 - FFFF)
S6-13
(3244)
Expert
EMOVR Option Fault ON Sets the bit to enable fault detection during Emergency Override.
bit 0 : bUS - Option Communication
bit 1 : CE - Communication Error
bit 2 : E5 - SI-T3 Watch Dog Timer
bit 3 : EF0 - Option Card External Fault
bit 4 : PE1 - PLC Fault 1
bit 5 : PE2 - PLC Fault 2
bit 6 : nSE - Node Setup Error
bit 7 to 15 : Reserved
Note:
The drive sets the bits in Hex.
0
(0 - FFFF)
S6-14
(3245)
Expert
EMOVR Application 1 Fault
ON
Sets the bit to enable fault detection during Emergency Override.
bit 0 : EFx - External Faults
bit 1 : Reserved
bit 2 : HLCE - High Level Communications Error
bit 3 : bAT - HOA Keypad Battery Voltage Low
bit 4 : TiM - Keypad Time Not Set
bit 5 : bCE - Bluetooth Communication Fault
bit 6 : Reserved
bit 7 : Reserved
bit 8 : Reserved
bit 9 : MSL - Net Master Lost
bit 10 : VLTS - Thermostat Fault
bit 11 to 15 : Reserved
Note:
The drive sets the bits in Hex.
0
(0 - FFFF)