5-6
E1-04
Max.
output
frequency
(FMAX)
To set V/f characteristics in a straight
line, set the same values for E1-07 and
E1-09. In this case, the setting for E1-
08 will be disregarded.
Always ensure that the four frequen-
cies are set in the following manner:
E1-04 (FMAX) E1-06 (FA) > E1-07
(FB) E1-09 (FMIN)
40.0 to
400.0
*7
50.0 Hz
*4
NoQQQQQ303H
最高输出频
E1-05
Max.
voltage
(VMAX)
0.0 to
255.0
*3
200.0
V
*3*4
NoQQQQQ304H
最大电压
E1-06
Base fre-
quency
(FA)
0.0 to
400.0
*7
50.0 Hz
*4
NoQQQQQ305H
基本频率
E1-09
Min. out-
put fre-
quency
(FMIN)
0.0 to
400.0
*7
0.5 Hz
*4
NoQQQAQ308H
最低输出频
E1-13
Base
voltage
(VBASE)
Change this setting only when making
advanced adjustments for V/f in the
fixed outputs area. Normally, there is
no need to make these settings.
0.0 to
255.0
*3
0.0 V
*5
NoAAQQQ30CH
基本电压
E2-01
Motor
rated cur-
rent
Set the motor rated current in amps.
This set value becomes the base value
for motor protection, torque limit, and
torque control. It is set automatically
when using autotuning.
0.32 to
6.40
*6
1.90 A
*2
NoQQQQQ30EH
电机额定电
E2-04
Number of
motor
poles
Set the number of motor poles. The
value is set automatically during auto-
tuning.
2 to 48 4 poles No No Q No Q Q 311H
电机极数
E2-11
Motor
rated
output
Set the output of the motor in units of
0.01kW. This constant is automatically
set during autotuning.
0.00 to
650.00
0.40
*8
NoQQQQQ318H
电机额定功
F1-01
PG con-
stant
Set the number of pulses per rotation
for the PG (pulse generator or
encoder) being used. (Do not set as a
multiple.)
0 to
60000
600 No No Q No Q No 380H
PG 脉冲数
H4-02
Gain (ter-
minal FM)
Set the voltage level gain for multi-
function analog output 1.
Set the number of multiples of 10 V to
be output as the 100% output for the
monitor items. Voltage output from the
terminals, however, have a 10 V max.
meter calibration function.
*13
0.00 to
2.50
1.00 Yes Q Q Q Q Q 41EH
端子 FM
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Display
V/f
V/f
with
PG
Open
-loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
Output voltage (V)
Frequency (Hz)
VMAX
(E1-05)
(V BASE)
(E1-13)
VC
(E1-08)
VMIN
(E1-10)
FMIN
(E1-09)
FB
(E1-07)
FA
(E1-06)
FMAX
(E1-04)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA varispeed G7 CIMR-G7B series and is the answer not in the manual?

YASKAWA varispeed G7 CIMR-G7B series Specifications

General IconGeneral
BrandYASKAWA
Modelvarispeed G7 CIMR-G7B series
CategoryInverter
LanguageEnglish

Related product manuals