îš‹ Operation Selection After Cooling Fan Fault
Use the constant setting to select the operation of the motor after a cooling fan fault occurs. This function can
be used for times when a motor should not be stopped quickly (with an emergency stop.)
A cooling fan equipped for 200 V Class Inverters of 7.5 kW, 15 kW, and 30 to 110 kW, and 400 V Class
Inverters of 5.5 to 15 kW and 55 to 300 kW.
Related Constants
The following table describes the operation of the motor and the display of the Digital Operator in accordance
with the settings of the L8-32 if a cooling fan fault occurred.
* If L8-32 is set to 0, the motor will continue running even if a cooling fan fault occurred. However, the Inverter rated output current and the
overload capacity will be reduced. The rated output current will be reduced to 80% if the normal rated output current is 100%, and the overload
capacity will be reduced to the values as follows.
When CT is selected: 100% per every 3 minutes, 150% per every 15 seconds
When VT is selected: 100% per every 30 seconds, 120% per every 10 seconds
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vector
2
L8-32
OH1 detection
of Inverter’ s
cooling fan
0: Disabled (FAN minor fault
detection)
1: Enabled (OH1 major fault
detection)
0 or 1 1 No A A A A
A
4E2H
OH1 检出选择
Setting
Value
Fault Digital Operator Motor Operation
Multi-function Con-
tact Output
0
Cooling Fin Overheating OH1 (lit) Coast to a stop Fault
Inverter’s Cooling Fan Fault FAN (blink)
Continue operation
*
Minor fault
1
Cooling Fin Overheating OH (lit) Coast to a stop Fault
Inverter’s Cooling Fan Fault OH1 (lit) Coast to a stop Fault
If L8-32 is set to 0, be sure to set H2-01 to H2-03 multi-function contact outputs to 10 (minor fault) or to 3D
(Inverter’s cooling fan fault.) If a cooling fan fault occurs, stop the Inverter immediately and replace the cool-
ing fan. If the Inverter continues to run while a cooling fan fault occurs, the Inverter’s cooling ability will be
affected and the Inverter’s internal temperature will increase and shorten the Inverter’s life.
During a cooling fan fault, the cooling fan stops for about 3 seconds every minute (interval operation.)