6-22
Accelerating and Decelerating Heavy Loads (Dwell Function)
The dwell function stores the output frequency when starting or stopping heavy loads. By temporarily storing
the output frequency, you can prevent the motor from stalling. When using the dwell function, you must select
a deceleration stop. Set b1-03 (Stopping Method Selection) to 0.
Related Parameters
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vector
2
b6-01
Dwell fre-
quency at
start
The dwell function is used to
output frequency temporarily
when driving a motor with a heavy
load.
0.0 to
400.0
0.0 Hz No A A A A A 1B6H
起动暂停频
b6-02
Dwell time
at start
0.0 to
10.0
0.0 s No A A A A A 1B7H
起动暂停时
b6-03
Dwell fre-
quency at
stop
0.0 to
400.0
0.0 Hz No A A A A A 1B8H
停止暂停频
b6-04
Dwell time
at stop
0.0 to
10.0
0.0 s No A A A A A 1B9H
停止暂停时
Run command ON
Output frequency
Timeb6-03
OFF
b6-01
b6-04
b6-02

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA varispeed G7 CIMR-G7B series and is the answer not in the manual?

YASKAWA varispeed G7 CIMR-G7B series Specifications

General IconGeneral
BrandYASKAWA
Modelvarispeed G7 CIMR-G7B series
CategoryInverter
LanguageEnglish

Related product manuals