5-72
* 1. When the control method is changed, the factory setting will change. The flux vector factory setting is given.
* 2. The factory setting depends on the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given.
o: Digital Operator Constants
The following settings are made with the Digital Operator constants (o constants): Multi-function selections
and the copy function.
Monitor Select: o1
User constants for Digital Operator Displays are shown in the following table.
N5-02
Motor accel-
eration time
Set the time required to
accelerate the motor at the
rated torque (T
100
) to the
rated speed (Nr).
J: GD
2
/4, P: Motor rated out-
put
However,
0.001
to
10.000
0.178 s
*2
No No No No A A 5B1H
4-21
6-142
电机加速时间
N5-03
Feed forward
proportional
gain
Set the proportional gain for
feed forward control.
Speed reference response will
increase as the setting of N5-
03 is increased.
0.00 to
100.00
1.0 No No No No A A 5B2H
4-21
6-142
制P增
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
o1-01
Monitor
selection
Set the number of the monitor
item to be displayed in the
earliest 4 monitor items. (U1-
)
The output monitor voltage
(factory setting) can be
changed.
4 to 99 6 Yes A A A A A 500H -
显示项目选择
o1-02
Monitor
selection after
power up
Sets the monitor item to be
displayed when the power is
turned on.
1: Frequency reference
2: Output frequency
3: Output current
4: The monitor item set for
o1-01
1 to 4 1 Yes A A A A A 501H 6-148
通电监视项目
选择
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
2π x J [kgm
2
] x Nr [min
-1
]
ta =
60
x T
100
[N x m]
[s]
T
100
=
× 10
3
[N x m]
60
2π
x
P [kW]
Nr [min
-1
]