Continuing Operation
6-71
Continuing Operation at Constant Speed When Frequency Reference Is
Lost
The frequency reference loss detection function continues operation using 80% speed of the frequency refer-
ence before loss when the frequency reference using a master speed analog input
*
is reduced 90% or more in
400 ms.
When the error signal during frequency reference loss is output externally, set H2-01 to H2-05 (multi-function
contact output terminal M1-M2, P1-PC, P2-PC, P3-C3, and P4-C4 function selection) to C (frequency refer-
ence lost).
* Frequency references using the following master speed analog inputs are used to detect a frequency loss.
Analog input using terminal A1
Analog input using terminal A2 when H3-09 (Multi-function analog input terminal A2 function selection) is set
to 0 (Add to terminal A1).
Related Constants
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vector
2
L4-05
Operation when
frequency refer-
ence is missing
0: Stop (Operation follows the
frequency reference.)
1: Operation at 80% speed
continues. (At 80% of speed
before the frequency reference
was lost)
Frequency reference is lost: Fre-
quency reference dropped over
90% in 400 ms.
0 or 1 0 No A A A A A 49DH