6-88
Monitor Constants
This section explains the analog monitor and pulse monitor constants.
Using the Analog Monitor Constants
This section explains the analog monitor constants.
Related Constants
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vector
2
H4-01
Monitor selec-
tion (terminal
FM)
Sets the number of the monitor
item to be output (U1-) from
terminal FM.
4, 10 to 14, 25, 28, 34, 39, 40 can-
not be set. 29 to 31 and 41 are not
used.
1 to 45 2 No A A A A A 41DH
端子 FM 设定
H4-02
Gain (terminal
FM)
Sets the multi-function analog
output 1 voltage level gain.
Sets whether the monitor item
output will be output in multiples
of 10 V.
The maximum output from the
terminal is 10 V. A meter calibra-
tion function is available.
0.00 to
2.50
1.00 Yes Q Q Q Q Q 41EH
端子 FM 增益
H4-03
Bias (terminal
FM)
Sets the multi-function analog
output 1 voltage level bias.
Sets output characteristic up/
down parallel movement as a per-
centage of 10 V.
The maximum output from the
terminal is 10 V. A meter calibra-
tion function is available.
-10.0
to
+10.0
0.0% Yes A A A A A 41FH
端子 FM 偏置
H4-04
Monitor selec-
tion (terminal
AM)
Sets the number of the monitor
item to be output (U1-) from
terminal AM.
4, 10 to 14, 25, 28, 34, 39, 40 can-
not be set. 29 to 31 and 41 are not
used.
1 to 45 3 No A A A A A 420H
端子 AM 设定
H4-05
Gain (terminal
AM)
Set the voltage level gain for
multi-function analog output 2.
Set the number of multiples of 10
V to be output as the 100% output
for the monitor items. The maxi-
mum output from the terminal is
10 V. A meter calibration function
is available.
0.00 to
2.50
0.50 Yes Q Q Q Q Q 421H
端子 AM 增益
H4-06
Bias (terminal
AM)
Sets the multi-function analog
output 2 voltage level bias.
Sets output characteristic up/
down parallel movement as a per-
centage of 10 V.
The maximum output from the
terminal is 10 V. A meter calibra-
tion function is available.
-10.0
to
+10.0
0.0% Yes A A A A A 422H
端子 AM 偏置
H4-07
Analog output 1
signal level
selection
Sets the signal output level for
multi-function output 1 (terminal
FM)
0: 0 to +10 V output
1: -10 to 10 V output
0 or 1 0 No A A A A A 423H
AO1 信号电平