Digital Operator Functions
6-151
Copying Constants
The Digital Operator can perform the following three functions using the built-in EEPROM (non-volatile
memory).
Store Inverter constant set values in the Digital Operator (READ)
Write constant set values stored in the Digital Operator to the Inverter (COPY)
Compare constant set values stored in the Digital Operator with Inverter constants (VERIFY)
Related Constants
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vector
2
o3-01
Copy function
selection
0: Normal operation
1: READ (Inverter to Operator)
2: COPY (Operator to Inverter)
3: Verify (compare)
0 to 3 0 No A A A A A 515H
拷贝功能选择
o3-02
Read permitted
selection
0: Read prohibited
1: Read permitted
0 or 1 0 No A A A A A 516H
读出许可选择

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA varispeed G7 CIMR-G7B series and is the answer not in the manual?

YASKAWA varispeed G7 CIMR-G7B series Specifications

General IconGeneral
BrandYASKAWA
Modelvarispeed G7 CIMR-G7B series
CategoryInverter
LanguageEnglish

Related product manuals