EasyManua.ls Logo

YASKAWA varispeed G7 CIMR-G7B series - Page 126

YASKAWA varispeed G7 CIMR-G7B series
495 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5-12
DC Injection Braking: b2
User constants for injection braking are shown in the following table.
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
b2-01
Zero-speed
level (DC
injection
braking start-
ing fre-
quency)
Used to set the frequency
which starts DC injection
braking in units of Hz when
deceleration to stop is
selected.
When b2-01 is less than E1-
09, E1-09 becomes the DC
injection braking starting fre-
quency.
0.0 to
10.0
0.5 Hz No A A A A A 189H
6-12
6-145
直流制动开始
频率
b2-02
DC injection
braking cur-
rent
Sets the DC injection braking
current as a percentage of the
Inverter rated current.
0 to
100
50% No A A A No No 18AH
6-12
6-16
直流制动电流
b2-03
DC injection
braking time
at start
Used to set the time to per-
form DC injection braking at
start in units of 1 second.
Used to stop coasting motor
and restart it. When the set
value is 0, DC injection brak-
ing at start is not performed.
0.00
to
10.00
0.00 s No A A A A A 18BH
6-13
6-16
起动制动时间
b2-04
DC injection
braking time
at stop
Used to set the time to per-
form DC injection braking at
stop in units of 1 second.
Used to prevent coasting after
the Stop Command is input.
When the set value is 0.00,
DC injection braking at stop
is not performed.
0.00
to
10.00
0.50 s No A A A A A 18CH 6-13
停止制动时间
b2-08
Magnetic flux
compensa-
tion volume
Sets the magnetic flux com-
pensation as a percentage of
the no-load current.
0 to
1000
0% No No No A No No 190H -
磁通量补偿

Table of Contents

Related product manuals