5-14
* The factory setting will change when the control method is changed. The open-loop vector 1 factory settings are given.
b3-10
Speed
search
detection
compensa-
tion gain
(speed cal-
culation)
Operation restarts at a speed
obtained by multiplying the
speed from the speed search by
the compensation gain (excita-
tion search only.)
Increase this setting if over-
voltages occur when a speed
search is performed after a
long baseblock, for example, in
searches at startup.
1.00 to
1.20
1.10 No A No A No A 19AH 6-65
搜索速度补
偿增益
b3-13
Propor-
tional gain
of the speed
estimator
during
speed search
Sets the proportional gain (PI
control) of the speed estimator
during speed search taking the
setting of N4-08 as equivalent
to a setting of 1.0.
Usually, there is no need to
change this setting. If, how-
ever, the load inertia is large
and overvoltages occur during
the search, reduce this setting.
Increase this setting for greater
speed coincidence response.
0.1 to
2.0
1.0% No No No No No A 19DH 6-66
速度推定比
例增益
b3-14
Rotation
direction
search
selection
0: Disabled (operates with
specified rotation direction)
1: Enabled (operates with
rotation direction found by
search)
0 or 1 1 No A A A No A 19EH 6-66
旋转方向搜
索选择
b3-17
Speed
search
retrial cur-
rent level
Sets the current level to retry a
speed search as a percentage,
taking the Inverter rated cur-
rent as 100%.
0 to
200
150% No A No A No A 1F0H 6-66
搜索重试 I
b3-18
Speed
search
retrial detec-
tion time
Sets the time for detection in a
speed search retrial in units of
seconds.
0.00 to
1.00
0.10 s No A No A No A 1F1H 6-66
速度搜索检
出时间
b3-19
Number of
speed search
retrials
Sets the number of times that a
speed search can be retried.
0 to 10 0 No A No A No A 1F2H 6-66
速度搜索重
试次数
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor