EasyManua.ls Logo

YASKAWA varispeed G7 CIMR-G7B series - Page 160

YASKAWA varispeed G7 CIMR-G7B series
495 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5-46
* The factory settings in the parentheses are for 3-wire sequence.
Multi-function Contact Input Functions
H1-10
Terminal S12
function selec-
tion
Multi-function contact input
10
0 to 79 15 No A A A A A 409H -
端子 S12 设定
Set-
ting
Value
Function
Control Methods
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
0 3-wire sequence (Forward/Reverse Run Command) Yes Yes Yes Yes Yes 6-11
1 Local/Remote selection (ON: Local, OFF: Remote) Yes Yes Yes Yes Yes 6-76
2 Option/Inverter selection (ON: Option board) Yes Yes Yes Yes Yes
6-83
6-164
3
Multi-step speed reference 1
When H3-05 is set to 0, this function is combined with the master/auxiliary speed
switch.
Yes Ye s Yes Yes Yes 6 - 5
4 Multi-step speed reference 2 Yes Yes Yes Yes Yes 6-5
5 Multi-step speed reference 3 Yes Yes Yes Yes Yes 6-5
6 Jog frequency command (higher priority than multi-step speed reference) Yes Yes Yes Yes Yes 6-5
7 Accel/decel time 1 Yes Yes Yes Yes Yes 6-19
8 External baseblock NO (NO contact: Baseblock at ON) Yes Yes Yes Yes Yes 6-77
9 External baseblock NC (NC contact: Baseblock at OFF) Yes Yes Yes Yes Yes 6-77
A
Acceleration/deceleration ramp hold (ON: Acceleration/deceleration stopped, fre-
quency on hold)
Yes Ye s Yes Yes Yes 6 - 7 8
B OH2 alarm signal input (ON: OH2 will be displayed) Yes Yes Yes Yes Yes -
C Multi-function analog input selection (ON: Enable) Yes Yes Yes Yes Yes -
D
No V/f control with PG (ON: Speed feedback control disabled,) (normal V/f con-
trol)
NoYesNoNoNo6-137
E Speed control integral reset (ON: Integral control disabled) No Yes No Yes Yes 6-137
F Not used (Set when a terminal is not used) - - - - - -
10 Up command (Always set with the down command) Yes Yes Yes Yes Yes 6-79
11 Down command (Always set with the up command) Yes Yes Yes Yes Yes 6-79
12 FJOG command (ON: Forward run at jog frequency d1-17) Yes Yes Yes Yes Yes 6-84
13 RJOG command (ON: Reverse run at jog frequency d1-17) Yes Yes Yes Yes Yes 6-84
14 Fault reset (Reset when turned ON) Yes Yes Yes Yes Yes 7-2
15
Emergency stop. (Normally open condition: Deceleration to stop in deceleration
time set in C1-09 when ON.)
Yes Ye s Yes Yes Yes 6 - 1 7
16 Motor switch command (Motor 2 selection) Yes Yes Yes Yes Yes -
17
Emergency stop (Normally closed condition: Deceleration to stop in deceleration
time set in C1-09 when OFF)
Yes Ye s Yes Yes Yes 6 - 1 7
18
Timer function input (Functions are set in b4-01 and b4-02 and the timer function
outputs are set in H1- and H2-.)
Yes Ye s Yes Yes Yes 6-105
19 PID control disable (ON: PID control disabled) Yes Yes Yes Yes Yes
6-109
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2

Table of Contents

Related product manuals