5-46
* The factory settings in the parentheses are for 3-wire sequence.
Multi-function Contact Input Functions
H1-10
Terminal S12
function selec-
tion
Multi-function contact input
10
0 to 79 15 No A A A A A 409H -
端子 S12 设定
Set-
ting
Value
Function
Control Methods
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
0 3-wire sequence (Forward/Reverse Run Command) Yes Yes Yes Yes Yes 6-11
1 Local/Remote selection (ON: Local, OFF: Remote) Yes Yes Yes Yes Yes 6-76
2 Option/Inverter selection (ON: Option board) Yes Yes Yes Yes Yes
6-83
6-164
3
Multi-step speed reference 1
When H3-05 is set to 0, this function is combined with the master/auxiliary speed
switch.
Yes Ye s Yes Yes Yes 6 - 5
4 Multi-step speed reference 2 Yes Yes Yes Yes Yes 6-5
5 Multi-step speed reference 3 Yes Yes Yes Yes Yes 6-5
6 Jog frequency command (higher priority than multi-step speed reference) Yes Yes Yes Yes Yes 6-5
7 Accel/decel time 1 Yes Yes Yes Yes Yes 6-19
8 External baseblock NO (NO contact: Baseblock at ON) Yes Yes Yes Yes Yes 6-77
9 External baseblock NC (NC contact: Baseblock at OFF) Yes Yes Yes Yes Yes 6-77
A
Acceleration/deceleration ramp hold (ON: Acceleration/deceleration stopped, fre-
quency on hold)
Yes Ye s Yes Yes Yes 6 - 7 8
B OH2 alarm signal input (ON: OH2 will be displayed) Yes Yes Yes Yes Yes -
C Multi-function analog input selection (ON: Enable) Yes Yes Yes Yes Yes -
D
No V/f control with PG (ON: Speed feedback control disabled,) (normal V/f con-
trol)
NoYesNoNoNo6-137
E Speed control integral reset (ON: Integral control disabled) No Yes No Yes Yes 6-137
F Not used (Set when a terminal is not used) - - - - - -
10 Up command (Always set with the down command) Yes Yes Yes Yes Yes 6-79
11 Down command (Always set with the up command) Yes Yes Yes Yes Yes 6-79
12 FJOG command (ON: Forward run at jog frequency d1-17) Yes Yes Yes Yes Yes 6-84
13 RJOG command (ON: Reverse run at jog frequency d1-17) Yes Yes Yes Yes Yes 6-84
14 Fault reset (Reset when turned ON) Yes Yes Yes Yes Yes 7-2
15
Emergency stop. (Normally open condition: Deceleration to stop in deceleration
time set in C1-09 when ON.)
Yes Ye s Yes Yes Yes 6 - 1 7
16 Motor switch command (Motor 2 selection) Yes Yes Yes Yes Yes -
17
Emergency stop (Normally closed condition: Deceleration to stop in deceleration
time set in C1-09 when OFF)
Yes Ye s Yes Yes Yes 6 - 1 7
18
Timer function input (Functions are set in b4-01 and b4-02 and the timer function
outputs are set in H1- and H2-.)
Yes Ye s Yes Yes Yes 6-105
19 PID control disable (ON: PID control disabled) Yes Yes Yes Yes Yes
6-109
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2