EasyManua.ls Logo

YASKAWA varispeed G7 CIMR-G7B series

YASKAWA varispeed G7 CIMR-G7B series
495 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User Constant Tables
5-53
Multi-function Analog Outputs: H4
User constants for multi-function analog outputs are shown in the following table.
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
H4-01
Monitor
selection
(terminal
FM)
Sets the number of the monitor
item to be output (U1-)
from terminal FM.
4, 10 to 14, 25, 28, 34, 39, 40
cannot be set. 29 to 31 and 41
are not used.
1 to 45 2 No A A A A A 41DH 6-88
端子 FM 设定
H4-02
Gain (ter-
minal FM)
Sets the multi-function analog
output 1 voltage level gain.
Sets whether the monitor item
output will be output in multi-
ples of 10 V.
The maximum output from the
terminal is 10 V. A meter cali-
bration function is available.
*
0.00 to
2.50
1.00 Yes Q Q Q Q Q 41EH
4-6
6-88
端子 FM 增益
H4-03
Bias (termi-
nal FM)
Sets the multi-function analog
output 1 voltage level bias.
Sets output characteristic up/
down parallel movement as a
percentage of 10 V.
The maximum output from the
terminal is 10 V. A meter cali-
bration function is available.
*
-10.0 to
+10.0
0.0% Yes A A A A A 41FH 6-88
端子 FM 偏置
H4-04
Monitor
selection
(terminal
AM)
Sets the number of the monitor
item to be output (U1-)
from terminal AM.
4, 10 to 14, 25, 28, 34, 39, 40
cannot be set. 29 to 31 and 41
are not used.
1 to 45 3 No A A A A A 420H 6-88
端子 AM 设定
H4-05
Gain (ter-
minal AM)
Set the voltage level gain for
multi-function analog output 2.
Set the number of multiples of
10 V to be output as the 100%
output for the monitor items.
The maximum output from the
terminal is 10 V. A meter cali-
bration function is available.
*
0.00 to
2.50
0.50 Yes Q Q Q Q Q 421H
4-6
6-88
端子 AM 增益
H4-06
Bias (termi-
nal AM)
Sets the multi-function analog
output 2 voltage level bias.
Sets output characteristic up/
down parallel movement as a
percentage of 10 V.
The maximum output from the
terminal is 10 V. A meter cali-
bration function is available.
*
-10.0 to
+10.0
0.0% Yes A A A A A 422H 6-88
端子 AM 偏置
H4-07
Analog out-
put 1 signal
level selec-
tion
Sets the signal output level for
multi-function output 1 (termi-
nal FM)
0: -10 to 10 V output
1: -10 to 10 V output
0 or 1 0 No A A A A A 423H 6-88
AO1 信号电

Table of Contents

Related product manuals