EasyManua.ls Logo

YASKAWA varispeed G7 CIMR-G7B series

YASKAWA varispeed G7 CIMR-G7B series
495 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User Constant Tables
5-63
Torque Detection: L6
User constants for the torque detection function are shown in the following table.
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
L6-01
Overtorque/
Under-
torque
detection
selection 1
0: Overtorque/undertorque
detection disabled.
1: Overtorque detection only
with speed agreement;
operation continues after
overtorque (warning).
2: Overtorque detected
continuously during
operation; operation
continues after overtorque
(warning).
3: Overtorque detection only
with speed agreement;
output stopped upon
detection (protected
operation).
4: Overtorque detected
continuously during
operation; output stopped
upon detection (protected
operation).
5: Undertorque detection only
with speed agreement;
operation continues after
overtorque (warning).
6: Undertorque detected
continuously during
operation; operation
continues after overtorque
(warning).
7: Undertorque detection only
with speed agreement;
output stopped upon
detection (protected
operation).
8: Undertorque detected
continuously during
operation; output stopped
upon detection (protected
operation).
0 to 8 0 No A A A A A 4A1H 6-53
转矩检出 1
动作
L6-02
Overtorque/
Under-
torque
detection
level 1
Open-loop vector control:
Motor rated torque is set as
100%.
V/f control: Inverter rated cur-
rent is set as 100%.
0 to
300
150% No A A A A A 4A2H 6-53
转矩检出 1
L6-03
Overtorque/
Under-
torque
detection
time 1
Sets the overtorque/under-
torque detection time in 1-sec-
ond units.
0.0 to
10.0
0.1 s No A A A A A 4A3H 6-54
转矩检出 1
时间

Table of Contents

Related product manuals