User Constant Tables
5-79
U1-13
Cumulative
operation
time
Monitors the total operating
time of the Inverter.
The initial value and the oper-
ating time/power ON time
selection can be set in o2-07
and o2-08.
(Cannot be output.)
1
hr
AA A A A 4CH
累积时间
U1-14
Software
No. (flash
memory)
(Manufacturers ID number) (Cannot be output.) - A A A A A 4DH
软件编号
U1-15
Terminal
A1 input
voltage
Monitors the input voltage of
the voltage frequency refer-
ence. An input of 10 V corre-
sponds to 100%.
10 V: 100% (10 V)
(-10 to 10 V possible)
0.1
%
AA A A A 4EH
端子 A1 电压
U1-16
Terminal
A2 input
current
(voltage)
Monitors the input current of
the multi-function analog
input.
An input of 20 mA corre-
sponds to 100%.
20 mA: 100% (4 to 20 mA)
(0 to 10 V, -10 to 10 V possi-
ble)
0.1
%
AA A A A 4FH
端子 A2 电压
U1-17
Terminal
A3 input
voltage
Monitors the input voltage of
the multi-function analog
input.
An input of 10 V corresponds
to 100%.
10 V: 100% (10 V)
(-10 to 10 V possible)
0.1
%
AA A A A050H
端子 A3 电压
U1-18
Motor sec-
ondary cur-
rent (Iq)
Monitors the calculated value
of the motor secondary cur-
rent.
The motor rated secondary
current corresponds to 100%.
10 V: Motor rated
secondary current)
(-10 to 10 V output)
0.1
%
A A A A A 51H
电机 2 次电
U1-19
Motor
exciting
current (Id)
Monitors the calculated value
of the motor excitation cur-
rent.
The motor rated secondary
current corresponds to 100%.
10 V: Motor rated
secondary current)
(-10 to 10 V output)
0.1
%
No No A A A 52H
电机励磁电
U1-20
Output fre-
quency
after soft-
start
Monitors the output frequency
after a soft start.
The frequency given does not
include compensations, such
as slip compensation.
The unit is set in o1-03.
10 V: Max. frequency
(-10 to 10 V possible)
0.01
Hz
A A A A A 53H
软起动输出
频率
U1-21
ASR input Monitors the input to the speed
control loop.
The maximum frequency cor-
responds to 100%.
10 V: Max. frequency
(-10 to 10 V possible)
0.01
%
No A No A A 54H
速度控制输
U1-22
ASR output Monitors the output from the
speed control loop.
The motor rated secondary
current corresponds to 100%.
10 V: Motor rated
secondary current)
(-10 to 10 V possible)
0.01
%
No A No A A 55H
速度控制输
U1-24
PID feed-
back value
Monitors the feedback value
when PID control is used.
The input for the max. fre-
quency corresponds to 100%.
10 V: Max. frequency
(-10 to 10 V possible)
0.01
%
A A A A A 57H
PID 反馈
Con-
stant
Number
Name
Description
Output Signal Level
During Multi-Function
Analog Output
Min.
Unit
Control Methods
MEMO-
BUS
Regis-
ter
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2