EasyManua.ls Logo

YASKAWA varispeed G7 CIMR-G7B series - Page 206

YASKAWA varispeed G7 CIMR-G7B series
495 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5-92
Note Attach a Momentary Power Interruption Compensation Unit if compensation for power interruptions of up to 2.0 seconds is required for 400 V Class Inverters
with outputs of 0.4 to 7.5 kW.
* 1. The initial settings for C6-02 are as follows: 1: 2.0 kHz, 2: 5.0 kHz, 3: 8.0 kHz, 4: 10.0 kHz, 5: 12.5 kHz, 6: 15.0 kHz, and F: optional setting (initial value for
Inverters of 90 or 110 kW: 3.0 kHz).
* 2. The initial settings for C6-11 are as follows: 1: 2.0 kHz, 2: 4.0 kHz, 3: 6.0 kHz, 4: 8.0 kHz.
* 3. The factory setting for 400V 132kW and 220kW flax vector control (A1-02 = 3) is 1.5 kHz, for software version VSG123032 or later.
Con-
stant
Number
Name Unit Factory Setting
- Inverter Capacity
kW 18.5 22 30 37 45 55 75 90 110 132 160 185 220 300
E2-11
Motor Rated
Capacity
E4-07
2nd Motor Rated
Capacity
o2-04 kVA selection - 2A 2B 2C 2D 2E 2F 30 31 32 33 34 35 36 37
b8-03
Energy-saving filter
time constant
s 0.50 (Open-loop vector control) 2.00 (Open-loop vector control)
b8-04
Energy-saving coeffi-
cient
-
115.74 103.58
92.54 76.32 71.56 67.20 46.20 38.91 36.23 32.79 30.13 30.57 27.13 21.76
C6-02
Carrier frequency
selection
*1
-3333322FF
F
*3
1
1F
*3
1
C6-11
Carrier frequency
selection for open-
loop vector 2 control
*2
-1111111111111 1
-
Carrier frequency
selection upper limit
-3333322
3.0 3.0
1111 1
E2-01
(E4-01)
Motor rated current A 32.9 38.6 52.3 65.6 79.7 95.0
130.0 156.0 190.0 223.0 270.0 310.0 370.0 500.0
E2-02
(E4-02)
Motor rated slip Hz 1.67 1.70 1.80 1.33 1.60 1.46 1.39 1.40 1.40 1.38 1.35 1.30 1.30 1.25
E2-03
(E4-03)
Motor no-load current A 7.8 9.2 10.9 19.1 22.0 24.0 36.0 40.0 49.0 58.0 70.0 81.0 96.0 130.0
E2-05
(E4-05)
Motor line-to-line
resistance
Ω
0.403 0.316 0.269 0.155 0.122 0.088 0.092 0.056 0.046 0.035 0.029 0.025 0.020 0.014
E2-06
(E4-06)
Motor leak inductance % 20.1 23.5 20.7 18.8 19.9 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0
E2-10
Motor iron loss for
torque compensation
W 508 586 750 925 1125 1260 1600 1760 2150 2350 2850 3200 3700 4700
L2-02
Momentary power
loss ridethru time
s 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
L2-03
Min. baseblock (BB)
time
s 1.0 1.1 1.1 1.2 1.2 1.3 1.5 1.7 1.7 1.8 1.9 2.0 2.1 2.1
L2-04 Voltage recovery time s 0.6 0.6 0.6 0.6 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
L8-02
Overheat pre-alarm
level
°C 95 95 95 95 95 100 105 105 120 110 115 100 110 115
L8-39
Reduced carrier
frequency
kHz 2.0 2.0 2.0 2.0 2.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
N1-03
Hunting-prevention
time constant
ms 10 10 10 10 10 30 30 30 30 30 30 100 100 100
N5-02
Motor acceleration
time
s
0.317 0.355 0.323 0.320 0.387 0.317 0.533 0.592 0.646 0.673 0.777 0.864 0.910 1.392

Table of Contents

Related product manuals