EasyManua.ls Logo

YASKAWA varispeed G7 CIMR-G7B series

YASKAWA varispeed G7 CIMR-G7B series
495 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Continuing Operation
6-65
Related Constants
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vector
2
b3-01
Speed search
selection (cur-
rent detection
or speed calcu-
lation)
Enables/disables the speed search
function for the Run Command
and sets the speed search method.
0:Disabled, speed calculation
1: Enabled, speed calculation
2: Disabled, current detection
3: Enabled, current detection
Speed Calculation:
When the search is started, the
motor speed is calculated and
acceleration/deceleration is
performed from the calculated
speed to the specified frequency
(motor direction is also
searched).
Current Detection:
The speed search is started from
the frequency when power was
momentarily lost and the
maximum frequency, and the
speed is detected at the search
current level.
0 to 3
2
*1
No A A A No A 191H
起动速度搜索
b3-02
Speed search
operating cur-
rent (current
detection)
Sets the speed search operation
current as a percentage, taking the
Inverter rated current as 100%.
Not usually necessary to set.
When restarting is not possible
with the factory settings, reduce
the value.
0 to
200
100%
*1
No A No A No A 192H
速度搜索电流
b3-03
Speed search
deceleration
time (current
detection)
Sets the output frequency deceler-
ation time during speed search in
1-second units.
Set the time for deceleration from
the maximum output frequency to
the minimum output frequency.
0.1 to
10.0
2.0 s No A No A No No 193H
搜索减速时间
b3-05
Speed search
wait time (cur-
rent detection
or speed calcu-
lation)
Sets the magnetic contactor oper-
ating delay time when there is a
magnetic contactor on the output
side of the Inverter. When a speed
search is performed after recover-
ing from a momentary power loss,
the search operation is delayed by
the time set here.
0.0 to
20.0
0.2 s No A A A A A 195H
搜索延迟时间
b3-10
Speed search
detection com-
pensation gain
(speed calcula-
tion)
Operation restarts at a speed
obtained by multiplying the speed
from the speed search by the com-
pensation gain.
Increase this setting if overvolt-
ages occur when speed search is
performed after a long baseblock,
for example, in searches at star-
tup.
1.00 to
1.20
1.10 No A No A No A 19AH
搜索速度补偿增

Table of Contents

Related product manuals