EasyManua.ls Logo

YASKAWA varispeed G7 CIMR-G7B series

YASKAWA varispeed G7 CIMR-G7B series
495 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7-4
UV2
控制回路
欠电压
Control Power Fault
The control power supply voltage
dropped.
The wiring of the control power cir-
cuit is incorrect.
A Backup Capacitor Unit for
Momentary Power Loss is not
attached to a 200 V/400 V Class
Inverter of 7.5 kW or less and the
value of the Momentary power loss
ridethru time (L2-02) factory setting
has been changed to the larger
value.
Try turning the power supply
off and on.
Replace the Inverter if the fault
continues to occur.
Attach a Backup Capacitor Unit
for Momentary Power Loss.
UV3
冲击防止
回路故障
Inrush Prevention Circuit Fault
A fault occurred in the surge preven-
tion circuit.
The magnetic contactor did not
respond for 10 s even though the mag-
netic contactor ON signal has been
output.
The magnetic contactor in the main
circuit failed.
The magnetic contactor excitation
coil is burned out.
Try turning the power supply
off and on.
Replace the Inverter if the fault
continues to occur.
PF
输入缺相
Main Circuit Voltage Fault
The main circuit DC voltage oscillates
unusually (not when regenerating).
This fault is detected if a load is
greater than approximately 80% of the
maximum motor capacity.
This fault is detected when L8-05 is
set to 1.
An open-phase occurred in the input
power supply.
A momentary power loss occurred.
The wiring terminals for the input
power supply are loose.
The voltage fluctuations in the input
power supply are too large.
The voltage balance between phases
is bad.
Reset the fault after correcting its
cause.
LF
输出缺相
Output Open-phase
An open-phase occurred at the
Inverter output.
This fault is detected when L8-07 is
set to 1 or 2
There is a broken wire in the output
cable.
There is a broken wire in the motor-
winding.
The output terminals are loose.
Reset the fault after correcting its
cause.
The motor being used has a capacity
less than 5% of the rated output cur-
rent.
Check the motor and Inverter
capacity.
OH
(OH1)
散热片
过热
Cooling Fin Overheating
The temperature of the Inverter's cool-
ing fins exceeded the setting in L8-02
or the overheat protection level.
OH: The temperature exceeded the
setting in L8-02 (Stopping method can
be changed by L8-03.).
OH1: The temperature exceeded
100°C (Stopping method: Coast to
stop).
The ambient temperature is too high. Install a cooling unit.
There is a heat source nearby. Remove the heat source.
The Inverter's cooling fan has stopped.
Replace the cooling fan. (Contact
our sales representative.)
A short-circuit between +V,
V, and
AC terminals occu
rred.
Overload in the control circuit ter-
minal.
Make sure that i
ncorrect wiring
has not been done.
Check the resistance and wir-
ing for the frequency setting
potentiometer, etc. (Check that
the current for terminals +V and
–V is 20 mA or less.)
Inverter's Cooling Fan Fault
(200 V Class: 7.5 kW or more,
400 V Class: 5.5 kW or more)
This fault is detected when L8-32 is
set to 1.
The Inverter's cooling fan has
stopped.
The heatsink is clogged.
Replace the cooling fan. (Con-
tact our sales representative.)
Clean the heatsink.
Table 7.1 Fault Displays and Processing (Continued)
Display Meaning Probable Causes Corrective Actions

Table of Contents

Related product manuals