EasyManua.ls Logo

YASKAWA varispeed G7 CIMR-G7B series

YASKAWA varispeed G7 CIMR-G7B series
495 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Wiring Control Circuit Terminals
2-25
* 1. For a 3-wire sequence, the default settings are a 3-wire sequence for S5, multi-step speed setting 1 for S6 and multi-step speed setting 2 for S7, and jog
frequency command for S8.
* 2. When driving a reactive load, such as a relay coil, always insert a flywheel diode as shown in Fig 2.17.
* 3. Pulse input specifications are given in the following table.
* 4. Use the photocoupler outputs when the minimum permissible load is 5 VDC or less and 10 mA or less.
Photo-
coupler
outputs
P1 Multi-function PHC output 1
Factory setting: Zero-speed
Zero-speed level (b2-01) or below when ON.
50 mA max. at 48 VDC
*2
P2 Multi-function PHC output 2
Factory setting: Frequency agreement detec-
tion
Frequency within 2 Hz of set frequency
when ON.
PC
Photocoupler output common
for P1 and P2
-
P3
Multi-function PHC output 3
Factory setting: Ready for operation when
ON.
C3
P4
Multi-function PHC output 4 Factory setting: Minor fault.
C4
Relay
outputs
MA
Fault output signal (NO con-
tact)
Fault when CLOSED across MA and MC
Fault when OPEN across MB and MC
Dry contacts
Contact capacity:
10 mA min. 1 A max. at
250 VAC
10 mA min. 1 A max. at
30 VDC
Minimum permissible
load: 5 VDC, 10 mA
*4
MB
Fault output signal (NC con-
tact)
MC
Relay contact output com-
mon
-
M1
Multi-function contact output
(NO contact)
Factory setting: Operating
Operating when ON across M1 and M2.
M2
Analog
moni-
tor out-
puts
FM
Multi-function analog moni-
tor 1
Factory setting: Output frequency
0 to 10 V/100% frequency
-10 to +10 VDC ±5%
2 mA max.AM
Multi-function analog moni-
tor 2
Factory setting: Current monitor
5 V/Inverter's rated current
AC Analog common -
Pulse
I/O
RP
Multi-function pulse input
*3
Factory setting: Frequency reference input
(H6-01 = 0)
0 to 32 kHz (3 kΩ)
MP Multi-function pulse monitor
Factory setting: Output frequency
(H6-06 = 2)
0 to 32 kHz (2.2 kΩ)
RS-
485/
422
R+
MEMOBUS communica-
tions input
For 2-wire RS-485, short R+ and S+ as well
as R- and S-.
Differential input, photo-
coupler isolation
R-
S+
MEMOBUS communica-
tions output
Differential output, pho-
tocoupler isolation
S-
IG Communications shield wire - -
Low level voltage 0.0 to 0.8 V
High level voltage 3.5 to 13.2 V
H duty 30% to 70%
Pulse frequency 0 to 32 kHz
Table 2.11 Control Circuit Terminals (Continued)
Type
No. Signal Name Function Signal Level

Table of Contents

Related product manuals