No. Name Description Values Page
Z3-03
(8502)
Serial Communications
Baud Rate Select
Selects the bypass serial communications speed.
0: 1200
<7>
1: 2400
<7>
2: 4800
<7>
3: 9600
4: 19200
5: 38400
6: 57600
7: 76800
8: 115200
Default: 3
Range: 0 to 8
215
Z3-04
(8503)
Serial Communications
Parity Select
Selects the bypass serial communications parity.
0: No Parity
1: Even Parity
2: Odd Parity
Default: 0
Range: 0 to 2
215
Z3-05
(8504)
Serial Communications
Fault Select
Selects the action to take when a serial communications fault is detected.
0: Ignore. A serial communications loss will result in no action being taken.
1: Alarm only.
2: Fault witn EF0. An EF0 will be sent to the drive. If running in Bypass, the
bypass contactor will NOT open and the motor will keep running.
3: Fault with EF0 and Open Contactors. An EF0 fault will be sent to the drive
and the bypass contactor (K3) will be opened.
4: Alarm and run at preset speed set in Z3-10. Display AL14 alarm on Operator
Default: 1
Range: 0 to 4
215
Z3-06
(8505)
Serial Communications
Fault Time Select
Sets the time allowed to elapse since receiving serial communications before
triggering a communications fault.
A setting of 0.0 will never time out.
Default: 2.0 s
Min.: 0.0
Max.: 99.9
428
Z3-07
(8506)
Serial Communications
Receive to Transmit Wait
Time
Sets the time to delay a serial communications response to a serial
communications command. This parameter will only appear when
Z3-01 = 0, 1, or 2.
Default: 5 ms
Min.: 0
Max.: 99 ms
428
Z3-08
(8507)
BACnet Device Object
Identifier 0
BACnet only.
Sets the least significant word of 22-bit virtual address. This parameter will
appear only when Z3-01 = 3.
Default: 1
Min.: 0
Max.: FFFF
216
Z3-09
(8508)
BACnet Device Object
Identifier 1
BACnet only.
Sets the most significant word of 22-bit virtual address. This parameter will
appear only when Z3-01 = 3.
Default: 0
Min.: 0
Max.: 003F
216
<1> Available in Quick Setting Group in bypass controller software versions VST800299 and earlier.
<2> Default setting is dependent on parameter o2-04, Drive Model Selection.
<3> Values shown are specific to 208 Vac. Double the value for 480 Vac.
<4> The number of decimal places in the parameter value depends on the drive model. Refer to Defaults by Drive Model on page 356 for details.
<5> Default value is 0 in bypass controller software versions VST800297 and earlier.
<6> Setting 2 is available in bypass controller software versions VST800298 and later.
<7> Selecting setting 0, 1, or 2 will trigger an oPE29 error when using BACNet communication in bypass controller software versions VST800400 and
later.
4.3 The Drive and Programming Modes
102
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual