No.
(Addr.
Hex)
Name Description Values Page
Z2-16
(8572)
Digital Input 8 Invert Select
0: Normal. Lack of input signal = OFF
1: Inverted. Lack of input signal = ON
Default: 0
Range: 0, 1
211
Z2-23
(8579)
Digital Output 7 Function
Select
Digital Output 1 Function Select
0: Serial Comm Controlled
1: K1 Drive Input Contactor
2: K2 Drive Output Contactor
3: K3 Bypass Contactor
4: K4 Motor 1 Select
5: K5 Motor 2 Select
6: READY (Drive and Bypass)
7: RUN Active (Drive or Bypass)
8: Drive RUN Active
9: Bypass RUN Active
10: HAND Mode Active
11: OFF Mode Active
12: AUTO Mode Active
13: Drive Mode Selected
14: Bypass Mode Selected
15: Drive or Bypass Fault Active
16: Drive Fault Active
17: Bypass Fault Active
18: Auto Transfer Active
19: Serial RUN Command Active
20: Damper Actuator Output
21: ON Always
22: Loss of Load Detected
23: Run Verify
<1>
24: Soft Start Run
<2>
99: Not Used
Default: 7
Range: 0 to 24; 99
212
Z2-24
(857A)
Digital Output 8 Function
Select
Default: 10
Range: 0 to 24; 99
212
Z2-25
(857B)
Digital Output 9 Function
Select
Default: 12
Range: 0 to 24; 99
212
Z2-26
(857C)
Digital Output 10 Function
Select
Default: 15
Range: 0 to 24; 99
212
Z2-31
(8581)
<1>
Safety Open Message
Selection
Sets the fault message displayed when an FB01 fault is triggered.
0: Safety Open
1: Fire Stat
2: Freeze Stat
3: Smoke Alarm
4: Over Pressure
5: Low Suction
6: Vibration Switch
Default: 0
Range: 0 to 6
212
<1> Available in bypass controller software versions VST800298 and VST800299.
<2> Available in bypass controller software versions VST800400 and later.
u
Z3: Bypass Control Communication
No.
(Addr.
Hex)
Name Description Values Page
Z3-01
(8500)
Serial Communications
Protocol Select
Selects the bypass serial communications protocol.
0: Modbus
1: N2
2: P1
3: BACnet
Default: 3
Range: 0 to 3
213
Z3-02
(8501)
Serial Communications
Node Address Select
Selects the bypass serial communications node address.
Default: 1
Min.: 0
Max.: 127
213
Z3-03
(8502)
Serial Communications
Baud Rate Select
Selects the bypass serial communications speed.
0: 1200 bps
<2>
1: 2400 bps
<2>
2: 4800 bps
<2>
3: 9600 bps
4: 19200 bps
5: 38400 bps
6: 57600 bps
7: 76800 bps
8: 115200 bps
Default: 3
Range: 0 to 8
215
B.14 Z: Bypass Parameters
352
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual