u
Bypass Nameplate
The nameplate is located on the inside right wall of the Z1000 Bypass enclosure.
The nameplate shown below is an example for a standard Z1000 Bypass.
A
A.C. INPUT
A.C. OUTPUT
Designator Rating
Serial No.:4W11X2888880001
Model No. :Z1B1D002PM
Type: Z1000 BYPASS
W.D.: DS.Z1B1.01
Inst. Manual:SIEPYAIZ1B01,
FGECC71061647A
F1,F2 FNQ-R1.5A,600V
Type
Volts: 208
Volts: 0-208
Hz: 50/60
Hz: 0-60
Phase: 3
Phase: 3
SCCR: 100kA rms sym.,208V max.
Amps: 2.9
Amps: 2.4
B
F
C
D
E
A Input specifications
B Output specifications
C Replacement fuse specifications
D Serial number
E Bypass model number
F Schematic document number
Figure 1.2 Bypass Nameplate Information Example
Z1B 1 B
Z1000
Bypass
No. Voltage
Refer to the following table
D 208 Vac
B 480 Vac
No. Enclosure Type
1 IP20/NEMA Type 1
040 P T
No. Control Options
D Ethernet/IP
L LonWorks
W Custom Nameplate
No. Power Options
B 3-Contactor Bypass
G Drive Service Switch
M Circuit Breaker
B/G
M
D/L
W
1.3 Model Numbers and Nameplate Checks
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual