Setting 0: Disabled
Setting 1: Enabled
u
Z2: Bypass Control Input/Output
n
Z2-01 to Z2-08: Digital Input 1 to 8 Function Select
No. Name Setting Range Default
Z2-01 Digital Input 1 Function Select 0 to 36 21
Z2-02 Digital Input 2 Function Select 0 to 36 22
Z2-03 Digital Input 3 Function Select 0 to 36 23
Z2-04 Digital Input 4 Function Select 0 to 36 24
Z2-05 Digital Input 5 Function Select 0 to 36 25
Z2-06 Digital Input 6 Function Select 0 to 36 0
Z2-07 Digital Input 7 Function Select 0 to 36 0
Z2-08 Digital Input 8 Function Select 0 to 36 29
n
Bypass Digital Input Terminal Settings
Table 5.28 Bypass Digital Input Terminal Settings
Setting Function Page
0
<1>
Unused (Available for Serial Comms)
Note: Multiple digital input terminals can
be programmed for “Unused
(Available for Serial Comms)”
(Z2-0o = 0). Set all other selections
only once in parameters Z2-01 to
Z2-08.
209
3 DRV Multi-Function Input S3 (H1-03 Setting) 209
4 DRV Multi-Function Input S4 (H1-04 Setting) 209
5 DRV Multi-Function Input S5 (H1-05 Setting) 210
6 DRV Multi-Function Input S6 (H1-06 Setting) 210
7 DRV Multi-Function Input S7 (H1-07 Setting) 210
21 Run (AUTO Mode) 210
22
<2>
Run Enable (Safety) 210
23 Run Interlock (BAS) 210
24 Remote Transfer to Bypass 210
25 Smoke Purge Bypass Run to Destruction 210
26
Smoke Purge Drive Run to Destruction at Smoke
Purge Preset Speed
210
Setting Function Page
27 Motor OR Select 210
28 Motor AND Select 210
29 Motor 1 Overload Contact 210
30 Motor 2 Overload Contact 210
31 HAND Select 210
32 AUTO Select 210
33 DRIVE/BYPASS Select 211
34 Fault Reset 211
35 External Fault (EF0) 211
36 External Fault (EFB) 211
38
<3>
Fire Stat (Safety) 211
39
<3>
Freeze Stat (Safety) 211
40
<3>
Smoke Alarm (Safety) 211
41
<3>
Over Pressure (Safety) 211
42
<3>
Low Suction (Safety) 211
43
<3>
Vibration Switch (Safety) 211
<1> Can be set to multiple digital input parameters simultaneously.
<2> Can be set to multiple digital input parameters simultaneously in bypass controller software versions VST800298 and VST800299 only. The drive
will run only when all digital inputs programmed for “22” are active.
<3> Available in bypass controller software versions VST800400 and later.
Setting 0: Unused (Available for Serial Comms)
Input terminals programmed to this value will have no effect on the operation of the bypass package. It is possible, however,
to read the status of the terminal over various serial communications protocols.
Note:
Multiple digital input terminals can be programmed for “Unused (Available for Serial Comms)” (Z2-0o = 0) in bypass controller software
versions VST800298 and later. All other selections should only be set once in parameters Z2-01 to Z2-08.
Setting 3: DRV Multi-Function Input S3 (H1-03 Setting)
Refer to H1-03 to H1-07: Functions for Terminals S3 to S7 on page 151 for available H1-03 multi-function input settings.
Setting 4: DRV Multi-Function Input S4 (H1-04 Setting)
Refer to H1-03 to H1-07: Functions for Terminals S3 to S7 on page 151 for available H1-04 multi-function input settings.
5.15 Z: Bypass Parameters
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual
209