YASKAWA Z1000 - Setting 4: Cooling Tower Fan Application; Setting 5: Cooling Tower Fan with PI Control Application

YASKAWA Z1000
466 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
No. Parameter Name Default Setting
C1-01 Acceleration Time 1 60 s
H3-01 Terminal A1 Signal Level Selection 2: 4 to 20 mA
H3-02 Terminal A1 Function Selection B: PI feedback
H3-10 Terminal A2 Function Selection 16: Differential PI feedback
L5-01 Number of Auto Restart Attempts 10
L6-01 Stall Prevention Selection during Deceleration 5: UL3 at speed agree (Alarm)
o1-07 Second Line Monitor Selection 505: PI Differential Feedback
u
Setting 4: Cooling Tower Fan Application
Table 4.9 Cooling Tower Fan: Parameter Settings
No. Parameter Name Default Setting
b1-03 Stopping Method Selection 1: Coast to Stop
b1-04 Reverse Operation Selection 0: Reverse operation enabled
b2-09
<1>
Motor Pre-Heat Current 2 10%
C1-01 Acceleration Time 1 60 s
d2-03 Master Speed Reference Lower Limit 30%
H1-07 Multi-Function Digital Input Terminal S7 Function Selection 60: Motor Pre-Heat 1
L5-01 Number of Auto Restart Attempts 10
L6-01 Stall Prevention Selection during Deceleration 5: UL3 at speed agree (Alarm)
<1> Details on this function can be found in the standard Z1000 Programming Manual (SIEPC71061645) at www.yaskawa.com.
u
Setting 5: Cooling Tower Fan with PI Control Application
Table 4.10 Cooling Tower Fan with PI Control: Parameter Settings
No. Parameter Name Default Setting
b1-03 Stopping Method Selection 1: Coast to Stop
b1-04 Reverse Operation Selection 0: Reverse operation enabled
b2-09
<1>
Motor Pre-Heat Current 2 10%
b5-01 PI Function Setting 1: Output frequency = PI output 1
b5-03 Integral Time Setting (I) 30 s
b5-08 PI Primary Delay Time Constant 2 s
b5-09 PI Output Level Selection 1: Reverse Output
b5-13 PI Feedback Low Detection Level 2%
b5-14 PI Feedback Low Detection Time 25 s
b5-15 PI Sleep Function Start Level 10.8 Hz
b5-16 PI Sleep Delay Time 25.5 s
C1-01 Acceleration Time 1 60 s
d2-03 Master Speed Reference Lower Limit 30%
H1-07 Multi-Function Digital Input Terminal S7 Function Selection 60: Motor Pre-Heat 1
L5-01 Number of Auto Restart Attempts 10
L6-01 Stall Prevention Selection during Deceleration 5: UL3 at speed agree (Alarm)
<1> Details on this function can be found in the standard Z1000 Programming Manual (SIEPC71061645) at www.yaskawa.com.
4.6 Application Selection
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual
109
4
Start-Up Programming
& Operation