A.5 Bypass Options
This following configurations are available for the Z1000 Bypass.
u
Option B
Three-contactor bypass: Isolates the drive circuit by adding a separate drive input contactor.
u
Option D
Ethernet/IP option.
u
Option M
Motor Circuit Protector (MCP)/Disconnect: Replaces the standard input disconnect switch and provides short circuit protection
integral with the drive and bypass package. The MCP includes a feature to padlock the operator mechanism through the door.
Without this option, short circuit protection must be provided by others on the input side of the drive and bypass.
u
Option G
Drive Input Disconnect Switch: Provides a disconnect means for the input side of the Drive, for Drive isolation capability
during bypass operation. This disconnect is located inside the enclosure with an integral operating handle.
u
Option L
Serial Communication, Echelon LonWorks: An isolated circuit board provides LonTalk protocol for network communication
to a BAS. This option plugs into the CN5 connection on the bypass control circuit board.
u
Option W
Custom Nameplate: Provides a custom nameplate for placement on the front of the Z1000 Bypass.
A.5 Bypass Options
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual
309