Object ID Object Name
Modbus
Address
Active Text Inactive Text PV Access
BV92 BYP Remote Xfer Stat 8785H: bit 4 ACTIVE OFF R
BV93 BYP Energy Save Stat 8785H: bit 5 ACTIVE OFF R
BV94 BYP Motor 1 Sel Stat 8785H: bit 6 SELECT OFF R
BV95 BYP Motor 2 Sel Stat 8785H: bit 7 SELECT OFF R
BV96 BYP Drive Flt Status 8786H: bit 0 FAULT OFF R
BV97 BYP Safety Flt Stat 8786H: bit 1 FAULT OFF R
BV98 BYP BAS ILock Status 8786H: bit 2 FAULT OFF R
BV99 BYP Ext Fault Stat 8786H: bit 3 FAULT OFF R
BV100 Not Used BV100 8786H: bit 4 FAULT OFF R
BV101 BYP Motor OL Stat 8786H: bit 5 FAULT OFF R
BV102 BYP Motor 1 OL Stat 8786H: bit 6 FAULT OFF R
BV103 BYP Mtr 2 OL Stat 8786H: bit 7 FAULT OFF R
BV104 BYP Input Phase Loss 8787H: bit 0 FAULT OFF R
BV105 BYP Drive Comms 8787H: bit 2 FAULT OFF R
BV106 BYP Loss Of Load 8787H: bit 5 FAULT OFF R
BV107 BYP Option Brd Comms 8787H: bit 3 FAULT OFF R
<1> Refer to Accessing Bypass Parameters and the Enter Command on page 374 for an explanation of how to read and write drive parameters not
listed in the analog or binary objects.
<2> Object is disabled when Z3-12 is set to 0 in bypass controller software versions VST800298 and later.
u
Device Object
The Device Object fully describes the BACnet device to the network. Notable is that the Device Object Instance ID and the
Device Object Name are configurable.
The Device Object Instance ID is a unique internetwork-wide numerical value. It is a 22-bit value that can range from 0 to
4,194,303. It is configurable by parameters Z3-08 and Z3-09. Any changes to these parameters will not take effect until the
power is cycled to the bypass.
The Device Object Name is a unique internetwork-wide character string. It is a 20-character string. It is writable from the
BACnet network. Any new string written will not take effect until the power is cycled to the bypass.
C.6 BACnet Objects Supported
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual
373
C
BACnet
Communications