Object ID Object Name
Modbus
Address
Active Text Inactive Text PV Access
BV44 Over Torque Detect 002CH:bit 11 ON OFF R
BV45 Frequency Ref Lost 002CH:bit 12 ON OFF R
BV46 Retry Error 002CH:bit 13 ON OFF R
BV47 Modbus Comms Error 002CH:bit 14 ON OFF R
BV48 Modbus Timeout Error 002CH:bit 15 ON OFF R
BV49 CRC Error 003DH:bit 0 ON OFF R
BV50 Invalid Data Length 003DH:bit 1 ON OFF R
BV51 Parity Error 003DH:bit 3 ON OFF R
BV52 Overrun Error 003DH:bit 4 ON OFF R
BV53 Framing Error 003DH:bit 5 ON OFF R
BV54 Timeout Error 003DH:bit 6 ON OFF R
BV55
<1>
Parameter Accept 0910H:bit 0 ON OFF W
BV56
<1>
Parameter Enter 0900H:bit 0 ON OFF W
BV57 Drive Comms Error 002CH:bit 15 ON OFF R
BV58 BYP Run Fwd CMD 8400H: bit 0 ON OFF C
BV59 BYP Run Rev CMD 8400H: bit 1 ON OFF C
BV60 Not Used BV60 ON OFF R
BV61 BYP Xfer to BYP CMD 8400H: bit 3 ON OFF C
BV62 BYP Smok Prg BYP CMD 8400H: bit 4 ON OFF C
BV63 BYP Smok Prg DRV CMD 8400H: bit 5 ON OFF C
BV64 BYP Mtr OR Sel CMD 8400H: bit 6 ON OFF C
BV65 BYP Mtr AND Sel CMD 8400H: bit 7 ON OFF C
BV66 BYP Drive Select CMD 8400H: bit 9 ON OFF C
BV67 BYP Auto Select CMD 8400H: bit 10 ON OFF C
BV68 Not Used BV68 8400H: bit 11 ON OFF C
BV69 BYP BYPASS Sel CMD 8400H: bit 12 BYP DRV C
BV70 BYP Fault Reset CMD 8400H: bit 13 ON OFF C
BV71 BYP Ext Fault CMD 8400H: bit 14 ON OFF C
BV72
<2>
BYP DI-01 Command 8402H: bit 0 ON OFF W
BV73
<2>
BYP DI-02 Command 8402H: bit 1 ON OFF W
BV74
<2>
BYP DI-03 Command 8402H: bit 2 ON OFF W
BV75
<2>
BYP DI-04 Command 8402H: bit 3 ON OFF W
BV76
<2>
BYP DI-05 Command 8402H: bit 4 ON OFF W
BV77
<2>
BYP DI-06 Command 8402H: bit 5 ON OFF W
BV78
<2>
BYP DI-07 Command 8402H: bit 6 ON OFF W
BV79
<2>
BYP DI-08 Command 8402H: bit 7 ON OFF W
BV80 BYP HAND Mode Status 8784H: bit 0 ON OFF R
BV81 BYP OFF Mode Status 8784H: bit 1 ON OFF R
BV82 BYP AUTO Mode Status 8784H: bit 2 ON OFF R
BV83 BYP DRV Mode Status 8784H: bit 3 ON OFF R
BV84 BYP BYPASS Mode Stat 8784H: bit 4 ON OFF R
BV85 BYP Smk Prg BYP Stat 8784H: bit 5 ACTIVE OFF R
BV86 BYP Smk Prg DRV Stat 8784H: bit 6 ACTIVE OFF R
BV87 BYP Safety Status 8784H: bit 7 OPEN CLOSED R
BV88 BYP BAS Interlk Stat 8785H: bit 0 OPEN CLOSED R
BV89 BYP RUN Status 8785H: bit 1 RUN OFF R
BV90 BYP Fault Status 8785H: bit 2 FAULT OFF R
BV91 BYP Auto Xfer Status 8785H: bit 3 ACTIVE OFF R
C.6 BACnet Objects Supported