B.7 F: Options
F parameters control the communication between the drive and the bypass.
u
F6: Drive/Bypass Communications
No.
(Addr.
Hex)
Name Description Values Page
F6-01
(03A2)
Communication Error
Operation Selection
Selects the drive behavior when the drive detects a CE fault.
0: Ramp to Stop. Decelerate to stop using the deceleration time in C1-02.
1: Coast to Stop.
2: Fast-Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm only.
4: Alarm (d1-04)
Default: 1
Range: 0 to 4
150
F6-02
(03A3)
External Fault from Bypass
Controller Detection
Selection
EF0 Detection
Selects when the drive should detect an EF0 fault issued by the bypass
controller.
0: Always detected
1: Only during run
Default: 0
Range: 0, 1
150
F6-03
(03A4)
External Fault from Bypass
Controller Operation
Selection
EF0 Action
0: Ramp to Stop. Decelerate to stop using the deceleration time in C1-02.
1: Coast to Stop.
2: Fast-Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm Only.
Default: 1
Range: 0 to 3
150
B.7 F: Options
322